CUT ALONG DOTTED LINE
Power Supply/Chargers Operating Guide
Models Include:
Model
Input
220VAC,
50/60Hz
Output
Auxiliary Power-Limited
Output (unswitched)
Ripple
Voltage
12VDC
24VDC
eFlow6NV,
eFlow6N8V, eFlow6N8DV,
eFlow6N16V, eFlow6N16DV
2.1A
6A
6A
1A
910mV
eFlow6NXV,
eFlow6NX8V, eFlow6NX8DV,
eFlow6NX16V, eFlow6NX16DV
Overview:
The eFlow6NV series power supply/chargers convert a 220VAC, 50/60Hz input to a 12VDC or 24VDC output.
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications Stand-by
7AH
0.4A/6A
N/A
10 Mins./6A
12AH
1A/6A
0.3A/6A
25 Mins./6A
40AH
6A/6A
1.2A/6A
Over 4 Hours/6A
65AH
6A/6A
1.5A/6A
Over 4 Hours/6A
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when AC fails.
Transfer to stand-by battery power is instantaneous with no interruption.
LED Diagnostics:
Red (DC)
Green (AC/AC1) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Installing Company: _______________ Service Rep. Name: __________________________________
Address: _____________________________________________ Phone #: __________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow6NV Series, Rev. 6NVRP052213 for
complete instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 6NVRP052213