UP2500

 | Manual

 

9

 

 

Idle 

 

 

Only current SOC status LED slowly flash. 

Charge 

 

Only current SOC status LED solid. 

Float 

charge 

●●●●

 

SOC

99%, 0.1A

  Current 

0.5A 

Highest SOC status LED solid, others flash per sec. 

Discharge 

100-76

●●●●

→  75

-51%

●●● 

→ 50

-26%

●●

 

 

25-0%

 

Residual SOC LEDs flash per sec. 

Soft start 

 

 

 

 

All SOC LEDs solid, pre-charge circuit is working. 

Alarm 

-

 

 

Show SOC

 

Alarm:  high  Voltage,  Low  Voltage,  Cell 

High/Low Temperature, MOS high temperature, 

high current.

 

 

Low SOC (

SOC≤10% 

or single cell voltage

≤3V

). 

Protection 

 

 

 

 

 

 

Charge MOS OFF. 

Possible  reason:  charging  over  current;  Over 

Voltage. 

 

 

 

 

 

 

Discharge MOS OFF. 

Possible  reason:  discharging  over  current;  Low 

Voltage; Short circuit; Reverse polarity. 

 

 

 

 

 

 

Charge and discharge MOS all OFF. 

Possible  reason:  Over/Low  Temperature;  MOS 

Over Temperature; BMS error. 

 

 

Show SOC 

Internal communication error,   

Address assignment error. 

 

 

 

 

 

 

Critical failure

: MOSFAIL; FUSE broken.   

 : flash 1.5s off/0.5s on 

 / 

 / 

 : flash 1s off/1s on 

 / 

 / 

 : constant lighting 

ADD Switch                                                                                                                                                                                           

ADD Switch: 4 ADD switches, 

Dip1

 

to definite different baud rate. ”0”and”1”, refer to picture right. “0XXX” 

setup the baud rate 115200, and “1XXX” setup the 

baud rate 9600.   

The settings will be active only after  restart the 

battery. 

Using  RS485:  all  batteries  need  to  set  the  ADD 

switch. And should be the same. 

Using CAN: the ADD switch has no influence on CAN baud rate. 

1

 

 

 

0

 

Summary of Contents for PYLONTECH UP2500

Page 1: ...Lithium Ion storage system Pylontech UP2500 manual Version 1 3 Part number AKPLX124100BXA2U...

Page 2: ...uces UP2500 from Pylontech Please read this manual before you to install the battery and follow the instruction carefully during the installation process Any confusion please contact Pylontech immedia...

Page 3: ...3 1 Schematic Diagram of Solution 12 3 2 Danger label 12 3 3 Tools 13 3 4 Safety Gear 13 4 INSTALLATION AND OPERATION 14 4 1 Package Items 14 4 2 Installation Location 15 4 3 Grounding 16 4 4 Install...

Page 4: ...ration temperature or humidity range listed in manual 5 Do not expose cable outside 6 Do not connect power terminal reversely 7 All the battery terminals must be disconnected for maintenance 8 Please...

Page 5: ...r authorized by Pylontech We do not undertake any consequences or related responsibility which because of violation of safety operation or violating of design production and equipment safety standards...

Page 6: ...self discharge up to 6 months without charging it on shelf no memory effect excellent performance of shallow charge and discharge Working temperature range is from 10 to 55 Charging 0 55 discharging...

Page 7: ...5 Recommend Charge Discharge Current A 55 Max Charge Discharge Current A 85 Peak Charge Discharge Current A 100A 15sec Communication RS485 CAN Configuration max in 1 battery group 20pcs Working Temper...

Page 8: ...eck below table LED Indicators Instructions for the detailed definition Protection Protection light RED LED to show the battery is under BMS protection Combine with SOC LEDs to show which kind of prot...

Page 9: ...tage Discharge MOS OFF Possible reason discharging over current Low Voltage Short circuit Reverse polarity Charge and discharge MOS all OFF Possible reason Over Low Temperature MOS Over Temperature BM...

Page 10: ...between multiple parallel batteries and between master battery to host equipment CAN CAN Communication Terminal RJ45 port follow Pylontech Low voltage CANBUS protocol for communication between master...

Page 11: ...r each single module each terminal can achieve charging and discharging function It must keep pressing this Lock Button during pulling out the power plug BMS function Protection and Alarm Management a...

Page 12: ...UP2500 Manual 12 3 Safe handling of lithium batteries Guide 3 1 Schematic Diagram of Solution 3 2 Danger label...

Page 13: ...sulated tools to prevent accidental electric shock or short circuits If insulated tools are not available cover the entire exposed metal surfaces of the available tools except their tips with electric...

Page 14: ...ing and check the Packing List 1 For battery module package Two power cables and one communication cable for each battery package Grounding cable Two long power cables max current capacity 120A and on...

Page 15: ...floor is flat and level There are no flammable or explosive materials The ambient temperature is within the range from 10 C to 40 C The temperature and humidity is maintained at a constant level Ther...

Page 16: ...e of the battery pack 4 3 Grounding Grounding cables shall be 10AWG or higher yellow green cables After connection the resistance from battery grounding point to Ground connection point of room or ins...

Page 17: ...UP2500 Manual 17 4 4 Installation A Put battery modules into the cabinet and connect the cables 1 Put the battery into the cabinet follow below picture 2 Fix each module with the cabinet with 4 screws...

Page 18: ...UP2500 Manual 18 3 Connect the cables between battery modules including grounding cables follow below picture 4 Connect the cables to inverter...

Page 19: ...airs of external power cable connect as A D and B C For more than 2 pairs of external cable need split the battery module into another string to further handle the connection There shall be a manual d...

Page 20: ...Press the Start Button SW of master battery to power on all the battery LED light will be on after master battery starts If all the battery LED lights on and then off which means the battery system i...

Page 21: ...ove 55 or under 10 the battery could not work Solution turn off the battery module move battery to the normal operating temperature range between 10 and 55 b Over Current If current is 100A battery pr...

Page 22: ...ntaminated area and seek medical attention Contact with eyes Rinse eyes with flowing water for 15 minutes and seek medical attention Contact with skin Wash the affected area thoroughly with soap and w...

Page 23: ...ency Maintenance 1 It is required to charge the battery at least once every 6 months for this charge maintenance make sure the SOC is charged to higher than 90 2 Every year after installation The conn...

Page 24: ...UP2500 Manual 24 Rheinwaldstra e 34 78628 Rottweil Tel 0741 174510 Mail info effekta com...

Reviews: