background image

UP2500

 | Manual

 

11

 

 

Definition of RJ11 Port Pin

 

No.   

RS232 Pin 

GND 

RXD 

TXD 

GND 

 

 

Power Ter/-                                                                                                                                                                       

Power cable terminals: there are two pair of terminals with 

same function, one connects 

to  equipment,  the  other  one  paralleling  to  other  battery 

module 

for 

capacity 

expanding.  For  each  single  module,  each  terminal  can 

achieve 

charging 

and 

discharging function. 

 

It must keep pressing this Lock Button during pulling out 

the power plug.

 

 

BMS function: 

Protection and Alarm 

Management and Monitor 

Charge/Discharge Cut-off 

Cells Balance 

Charge Over Voltage 

Intelligent Charge Model 

Discharge Under Voltage 

Capacity Retention Calculate 

Charge/Discharge Over Current 

Administrator Monitor 

High/Low Temperature 

Operation Record 

Short Circuit 

Soft Start 

 

Hot Swap 

 

 

 

 

 

Summary of Contents for PYLONTECH UP2500

Page 1: ...Lithium Ion storage system Pylontech UP2500 manual Version 1 3 Part number AKPLX124100BXA2U...

Page 2: ...uces UP2500 from Pylontech Please read this manual before you to install the battery and follow the instruction carefully during the installation process Any confusion please contact Pylontech immedia...

Page 3: ...3 1 Schematic Diagram of Solution 12 3 2 Danger label 12 3 3 Tools 13 3 4 Safety Gear 13 4 INSTALLATION AND OPERATION 14 4 1 Package Items 14 4 2 Installation Location 15 4 3 Grounding 16 4 4 Install...

Page 4: ...ration temperature or humidity range listed in manual 5 Do not expose cable outside 6 Do not connect power terminal reversely 7 All the battery terminals must be disconnected for maintenance 8 Please...

Page 5: ...r authorized by Pylontech We do not undertake any consequences or related responsibility which because of violation of safety operation or violating of design production and equipment safety standards...

Page 6: ...self discharge up to 6 months without charging it on shelf no memory effect excellent performance of shallow charge and discharge Working temperature range is from 10 to 55 Charging 0 55 discharging...

Page 7: ...5 Recommend Charge Discharge Current A 55 Max Charge Discharge Current A 85 Peak Charge Discharge Current A 100A 15sec Communication RS485 CAN Configuration max in 1 battery group 20pcs Working Temper...

Page 8: ...eck below table LED Indicators Instructions for the detailed definition Protection Protection light RED LED to show the battery is under BMS protection Combine with SOC LEDs to show which kind of prot...

Page 9: ...tage Discharge MOS OFF Possible reason discharging over current Low Voltage Short circuit Reverse polarity Charge and discharge MOS all OFF Possible reason Over Low Temperature MOS Over Temperature BM...

Page 10: ...between multiple parallel batteries and between master battery to host equipment CAN CAN Communication Terminal RJ45 port follow Pylontech Low voltage CANBUS protocol for communication between master...

Page 11: ...r each single module each terminal can achieve charging and discharging function It must keep pressing this Lock Button during pulling out the power plug BMS function Protection and Alarm Management a...

Page 12: ...UP2500 Manual 12 3 Safe handling of lithium batteries Guide 3 1 Schematic Diagram of Solution 3 2 Danger label...

Page 13: ...sulated tools to prevent accidental electric shock or short circuits If insulated tools are not available cover the entire exposed metal surfaces of the available tools except their tips with electric...

Page 14: ...ing and check the Packing List 1 For battery module package Two power cables and one communication cable for each battery package Grounding cable Two long power cables max current capacity 120A and on...

Page 15: ...floor is flat and level There are no flammable or explosive materials The ambient temperature is within the range from 10 C to 40 C The temperature and humidity is maintained at a constant level Ther...

Page 16: ...e of the battery pack 4 3 Grounding Grounding cables shall be 10AWG or higher yellow green cables After connection the resistance from battery grounding point to Ground connection point of room or ins...

Page 17: ...UP2500 Manual 17 4 4 Installation A Put battery modules into the cabinet and connect the cables 1 Put the battery into the cabinet follow below picture 2 Fix each module with the cabinet with 4 screws...

Page 18: ...UP2500 Manual 18 3 Connect the cables between battery modules including grounding cables follow below picture 4 Connect the cables to inverter...

Page 19: ...airs of external power cable connect as A D and B C For more than 2 pairs of external cable need split the battery module into another string to further handle the connection There shall be a manual d...

Page 20: ...Press the Start Button SW of master battery to power on all the battery LED light will be on after master battery starts If all the battery LED lights on and then off which means the battery system i...

Page 21: ...ove 55 or under 10 the battery could not work Solution turn off the battery module move battery to the normal operating temperature range between 10 and 55 b Over Current If current is 100A battery pr...

Page 22: ...ntaminated area and seek medical attention Contact with eyes Rinse eyes with flowing water for 15 minutes and seek medical attention Contact with skin Wash the affected area thoroughly with soap and w...

Page 23: ...ency Maintenance 1 It is required to charge the battery at least once every 6 months for this charge maintenance make sure the SOC is charged to higher than 90 2 Every year after installation The conn...

Page 24: ...UP2500 Manual 24 Rheinwaldstra e 34 78628 Rottweil Tel 0741 174510 Mail info effekta com...

Reviews: