UP2500
| Manual
15
1)
Option: For battery system connects to inverters
:
The cables are not included in the standard scope of delivery and must be ordered separately.
Two long power cables (max. current capacity
120A
) and one communication cable for each
energy storage system:
4.2 Installation Location
Make sure that the installation location meets the following conditions:
◆
The area is completely waterproof
◆
The floor is flat and level.
◆
There are no flammable or explosive materials.
◆
The ambient temperature is within the range from 10°C to 40°C.
◆
The temperature and humidity is maintained at a constant level.
◆
There is minimal dust and dirt in the area.
◆
The distance from heat source is more than 2 meters.
◆
The distance from air outlet of inverter is more than 0.5 meters.
◆
The installation areas shall avoid of direct sunlight.
◆
There is no mandatory ventilation requirements for battery module, but please avoid of installation in
confined area. The aeration shall avoid of high salinity, humidity or temperature.
2000
3000