122
Rev.A 06/01/2012
UPS INPUT: RECTIFIER AND BATTERY CHARGER
POWER
kVA
30
40
Input
Three-phase + Neutral
Nominal input voltage range
Vac
%
400
-20/+15
Input frequency range
Hz
%
50
– 60
±5
Input power factor
> 0.99
Input current THD at nominal voltage
and THDV <0,5%
@25% load
@50% load
@75% load
@100% load
%
< 14
< 7
< 5
< 4
DC output voltage accuracy
%
+/- 1%
DC output voltage ripple
% rms
1% rms
Battery recharging characteristic
IU (DIN 41773)
Maximum recharging current
- at nominal load
A
10
8
Bridge rectifier type
IGBT PFC
Input protection
Fuses
Inrush input current
A
< maximum nominal current
Earth leakage current
mA
< 22
Nominal current absorbed from mains
(at nominal load and battery charged)
A
38
50
Maximum current absorbed from mains
(at nom. Load, max. recharging current and min. input
voltage)
A
58
72
Settable walk-in
sec
Sectable from
5’’ to 30’’
Settable hold-off
sec
Sectable from 1
’’ to 300’’
BATTERY
POWER
kVA
30
40
External battery
Standard type
Maintenance free
Cells number (settable)
2x180 or 2x186
Floating voltage at 25°C (settable)
Vdc
2x406 or 2x418
Minimum battery discharge voltage
Vdc
Settable
Inverter input power (at nominal load)
kW
25,4
34
Inverter input current
(at nominal load and minimum Vdc)
A
36
48
Battery Protection (external to the UPS)
Fuses
Battery Test
Included as standard