UPS user manual
Rev.A 05/15/2012
101
Alarm
A23
EPO PRESSED
Description
The system is blocked due to the activation of the emergency power off
button.
Possible
causes
Activation of the (local or remote) emergency power off button.
Solutions
1. Release the emergency power off button and reset the alarm.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A24
HIGH TEMPERATURE
Description
High temperature of the heat sink on the inverter bridge or tripping of
the DC fuses which protect the inverter bridge.
Possible
causes
Fault of the heat sink cooling fans.
The room temperature or cooling air temperature is too high.
Tripping of the DC protection fuses.
Solutions
1. Check the fans operation.
2. Clean the ventilation grids and the air filters, if any.
3. Check the air conditioning system (if present).
4. Check the status of the DC fuses on the inverter bridge input.
5. If the alarm persists, contact our Technical Support Service.
Alarm
A25
INVERTER OFF
Description
The inverter is blocked due an operation failure.
Possible
causes
Various.
Solutions
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
Alarm
A26
COMMUNIC ERROR
Description
Internal error.
Possible
causes
Microcontroller communication problems.
Solutions
1. If the alarm persists, contact our Technical Support Service.
Alarm
A27
EEPROM ERROR
Description
The controller has detected an error in the parameters stored in
EEPROM.
Possible
causes
Wrong parameters entered during programming.
Solutions
1. Contact our Technical Support Service.