
116
Rev.A 06/01/2012
UPS INPUT: RECTIFIER AND BATTERY CHARGER
POWER
kVA
10
15
20
Input
Three-phase + Neutral
Nominal input voltage range
Vac
%
400
-20/+15
Input frequency range
Hz
%
50
– 60
±5
Input power factor
> 0.99
Input current THD at nominal voltage
and THDV <0,5%
@25% load
@50% load
@75% load
@100% load
%
13 <
7 <
5 <
3 <
DC output voltage accuracy
%
+/- 1%
DC output voltage ripple
% rms
2% rms
Battery recharging characteristic
IU (DIN 41773)
Maximum recharging current
- at nominal load
A
6
10
6
Bridge rectifier type
IGBT PFC
Input protection
Fuses
Inrush input current
A
< maximum nominal current
Earth leakage current
mA
< 22
Nominal current absorbed from mains
(at nominal load and battery charged)
A
12
19
23
Maximum current absorbed from mains
(at nom. Load, max. recharging current and min. input
voltage)
A
24
36
36
Settable walk-in
sec
Sectable from
5’’ to 30’’
Settable hold-off
sec
Sectable from 1
’’ to 300’’
BATTERY
POWER
kVA
10
15
20
Maximum internal battery
60 or 62 batteries 3,3AH - 7,2AH - 9AH
Standard type
Maintenance free
Cells number (settable)
2x180 or 2x186
Floating voltage at 25°C (settable)
Vdc
2x406 or 2x418
Minimum battery discharge voltage
Vdc
Settable
Inverter input power (at nominal load)
kW
8,5
12,7
17
Inverter input current
(at nominal load and minimum Vdc)
A
12
18
24
Battery Protection (external to the UPS)
Fuses
Battery Test
Included as standard
Summary of Contents for PEGASUS II 10 KVA
Page 1: ...OPERATING MANUAL UPS PEGASUS II 10 20 30 40 kVA Rev A 05 15 2012 ...
Page 2: ......
Page 126: ...126 Rev A 06 01 2012 ...
Page 127: ...Rev A 06 01 2012 127 ...
Page 128: ...128 Rev A 06 01 2012 ...