UPS: MKD 700
– 3000 VA RT (XL)
Technical Data
13.
Technical data
MKD model:
700 RT
1000 RT
1500 RT
2000 RT
3000 RT
Po
w
er
Maximum power (kVA)
700
1000
1500
2000
3000
Maximum power (kW)
630
900
1350
1800
2700
In
pu
t
Nominal voltage
230 V AC
Input voltage range
120 VAC
– 276 VAC
THDi
< 5 % with linear load
Input Power Factor
0,99 with 100 % nominal load
Input frequency range
(45~55) / (54~66) Hz
O
ut
pu
t
Output voltage
208, 220, 230, 240 VAC
Voltage tolerance
± 1 %
Frequency tolerance
± 0,2 Hz (autonomous mode)
Voltage wave form
pure sine
Crest factor
3
(CREST FACTOR)
Switchover time standard mode
Network <> INVERTER:
0
ms
Switchover time (BY-PASS, ECO)
By-pass <> INVERTER: maximum
10
ms
Ef
fic
ie
nc
y
Efficiency rate
with full load
LINE MODE
> 89 % with charged battery bank
BATTERY MODE
> 84 %
ECO MODE
> 95 %
In
te
rn
al
ba
tte
ry
b
an
k
Battery type
12 VDC / 7 Ah
12 VDC / 9 Ah
Number of battery blocks
3
4
6
Battery bank voltage
36 VDC
48 VDC
72 VDC
Charging time
ca. 6 h to 80 %
Charging time for XL variants
Dependent on the external battery bank(s)
D
ev
ic
e
LC display
Backlit alphanumeric LC display
Communication
Intelligent adapter slot (for AS400, SNMP)
Device protection
Overload, deep discharge, overcharge
Device class
C2
Protection class
IP20
Housing
Sheet steel, plastic front panel
Weight with batteries (Standard)
16.2kg
16.2kg
19.7kg
19.7kg
28.6kg
Weight without batteries (XL
variants)
8.4kg
8.4kg
9.3kg
9.3kg
13.2kg