UPS: MKD 700
– 3000 VA RT (XL)
Operation and Service
6.
Operation of device and service
Due to the comprehensive protective functions which the device performs
regarding the loads, the UPS runs completely automatically. This reduces the
operation of the device to a few steps and this as well in the boundary of the
power. As a result, the operation of the UPS is d
ivided into “general operation”
and “maintenance or service operation.”
In general, the operating personnel should inform affected employees (keyword:
consumer network) about any scheduled tasks concerning the UPS system.
Have chapter 8
Meready to facilitate the immediate interpretation of the
operation display and possibly occurring errors.
6.1
Operation and performance of the UPS
As a rule, the switching on or starting up and shutting down of the system is
done by the operating personnel.
The operator of the UPS-system must always adhere to the instructions in this
operating manual. Only the operator can perform the following actions and must
always exercise particular care:
–
Switching the UPS on and off;
–
Reading the display messages and interpreting the acoustic warning
signals;
–
Switching from standard mode to autonomous mode and vice versa.
The operation of the UPS / system generally assumes that all previous chapters
in this operating manual have already been successfully processed and
controlled.
6.1.1
Switching on and starting the UPS device with the mains power supply
Starting the UPS device ensues through the following procedure. Observe the
indicated sequence for this:
The precondition is that a mains power supply does not exist.
The EPO (REPO connection) must be closed.