Photovoltaic Solar Inverter Series ES 

Assembly

 

 

 

ES series 

26 

 

 

The photovoltaic solar inverter is constructed for vertical assembly. 

 

Never assemble the photovoltaic solar inverter in a horizontal 
position and make sure it does not tilt forward if assembled outdoors. 

 

 

 

 

 

 

 
 

Fig. 4-2 - 2   

Ambient conditions for assembly (positioning) 

 

 

When selecting the assembly location for the photovoltaic solar 
inverter, you must ensure that there is sufficient heat dissipation.

 

The following minimum amounts of free space around the 
photovoltaic solar inverter must be maintained: 

 

 

 

 

 

 

 

 

 

 

 

 

Spacing of at least 20 cm 

Spacing of at least 5 cm 

 

Fig. 4-2 - 3   

Ambient conditions for assembly (spacings) 

Summary of Contents for ES2200

Page 1: ...taic Solar Inverter Series ES ES2200 ES3300 ES4200 ES5000 Operating Manual V 3 2 Article number SLWRABSI2K0Wx000 SLWRABSI3K0Wx000 SLWRABSI4K0Wx000 SLWRABSI5K0Wx000 Translation of the original Operatin...

Page 2: ...be copied or distributed in part or in full without our consent in writing nor can it be used without authorisation for competitive purposes or given or made accessible to third parties EFFEKTA Regel...

Page 3: ...y Damage 15 2 4 Protecting the environment 15 2 5 Connection 16 2 6 Advice about specific dangers 17 2 7 Operation 18 2 8 Working with PV modules 18 2 9 Maintenance Service and Malfunctions 19 2 10 Ad...

Page 4: ...tates of the photovoltaic solar inverter 52 8 Communication Interfaces 54 8 1 Standard communication interface 54 8 2 Solar LogTM 55 8 3 Optional data cards 55 9 Status Diagnosis and Troubleshooting 6...

Page 5: ...nual only relate to special requirements for the photovoltaic solar inverter During installation make sure you follow the national and local requirements for electrical installations The content of th...

Page 6: ...inity of the device at all times so it is immediately available if need be 1 4 Symbols in this Manual The abbreviation PV in this manual stands for photovoltaic Read this documentation carefully and m...

Page 7: ...h CAUTION provides a warning about hazards If accident prevention measures are not taken these dangerous situations can lead to slight or medium reversible injuries Text that is marked with ATTENTION...

Page 8: ...Warning information 1 4 2 1 Warning about danger spots General warning about danger spots 1 4 2 2 Specific warning Warning about dangerous electrical voltage 1 4 3 Instruction symbols Take note of th...

Page 9: ...er 2 Safety Instructions If the cross reference refers to a page figure or position number this information is added at the end of the cross reference Example Fig 4 4 Pos 1 This means See position num...

Page 10: ...ll as this declaration should also be given to the new owner if the device is passed on We guarantee that this device upon delivery is in a functional state and technically conforms to the description...

Page 11: ...this is done in the original packaging Incurred transport costs are generally not included in the warranty You shall bear the cost of repair and exchange and EFFEKTA Regeltechnik GmbH is not liable f...

Page 12: ...thout any limitation damage related to a loss of profits interruption of business loss of business information or any other losses that result from use of the device or are connected with the device w...

Page 13: ...is danger of condensation Before you take additional steps an acclimatisation period of at least 2 hours is to be observed Never place or operate the device in a moist environment Keep liquids away fr...

Page 14: ...ation of the safety requirements and instructions provided in this operating manual 2 2 Proper Use The photovoltaic solar inverter and its related components may only be used for purposes in accordanc...

Page 15: ...commissioning of the device Only operate the product in an appropriate and proper way and within the parameters stated in the technical data Only perform maintenance and service work that is describe...

Page 16: ...amage that is caused by reverse polarity Make sure that all connections are firmly in place since loose connections overheat and represent a potential danger The operation of the photovoltaic solar in...

Page 17: ...uipment of the device and the ancillary devices regularly In the case of damage to the electrical equipment of the device and the ancillary devices switch off immediately at the main switch es Have an...

Page 18: ...FFEKTA Regeltechnik GmbH Company is not liable for damage caused by this to the PV modules and to the photovoltaic solar inverter At 20 C the open circuit voltage of the PV modules may not be above 50...

Page 19: ...vice from the power supply parts of the photovoltaic solar inverter can still have high voltages 2 10 Advice about connecting to the mains power The photovoltaic solar inverter may only be connected t...

Page 20: ...ter Series ES Device Description ES series 20 3 Device Description 3 1 Dimensions ES2200 ES3300 ES4200 ES5000 H Height mm 430 510 W Width mm 455 455 D Depth mm 190 190 Fig 3 1 1 Dimensions of the phot...

Page 21: ...of the photovoltaic solar inverter 2 Data transmission interface to option USB RS485 floating contact TCP IP 3 AC output terminal AC output for power supply connection 4 Data transmission interface s...

Page 22: ...ovoltaic solar inverter 2 Data transmission interface option USB RS485 floating contact TCP IP 3 AC output terminal AC output for power supply connection 4 Data transmission interface standard RS232 5...

Page 23: ...4 1 Assembly of the wall mounting Before starting the assembly of the photovoltaic solar inverter take note of load bearing capacity of the wall There is a requirement for a load bearing capacity of a...

Page 24: ...Photovoltaic Solar Inverter Series ES Assembly ES series 24 Fig 4 1 2 Wall mounting for photovoltaic solar inverter ES4200 ES5000...

Page 25: ...mper the effectiveness and shorten the service life of the photovoltaic solar inverter If need be install an additional cooling system in the room in which the photovoltaic solar inverter is assembled...

Page 26: ...tilt forward if assembled outdoors Fig 4 2 2 Ambient conditions for assembly positioning When selecting the assembly location for the photovoltaic solar inverter you must ensure that there is sufficie...

Page 27: ...ries ES Assembly ES series 27 If the photovoltaic solar inverters are to be assembled above each other we recommend offsetting them because of the heat emissions 1 Spacing of at least 20 cm Fig 4 2 4...

Page 28: ...Inverter Series ES Assembly ES series 28 If the photovoltaic solar inverters are assembled directly above each other the spacings must be adhered to 1 Spacing of at least 50 cm Fig 4 2 5 Spacings wit...

Page 29: ...ting take into account the weight of the photovoltaic solar inverter See Chapter 11 Technical data You can use the wall mounting to mark the holes for drilling If you do not want to use the wall mount...

Page 30: ...ith the screws you have selected 3 Screw on the wall mounting Fig 4 3 1 4 Hang the photovoltaic solar inverter on the wall mounting Use the upper carrier plate so that the photovoltaic solar inverter...

Page 31: ...equipment in accordance with electrotechnical rules 2 Safety Instructions 1 String A 2 String B 3 Data transfer 4 AC output Fig 5 1 Wiring of the photovoltaic solar inverter Example ES4200 ES5000 Two...

Page 32: ...nection conditions Take note of the connection conditions of your mains power supplier Pay attention to the locally required country settings on the photovoltaic solar inverter 7 2 Country settings op...

Page 33: ...oltage and frequency of the supply mains Supply voltage and frequency are country specific In order to separate the photovoltaic solar inverter from the mains power and the PV modules a customer suppl...

Page 34: ...r still have a life threatening level of voltage charge You should make sure that all the sub assemblies and components of the photovoltaic solar inverter are voltage free before starting work Fig 5 1...

Page 35: ...Photovoltaic Solar Inverter Series ES Electrical Installation ES series 35 1 PE Grounding conductor yellow green 2 N Neutral 3 L Conductor Fig 5 1 4 Power cable connection...

Page 36: ...approx 50 of the total output of the inverter Of these tracker A has a connection for up to 2 strings and tracker B for one string The ES2200 ES3300 photovoltaic solar inverters have only one MPP tra...

Page 37: ...e take note of the symmetrical power distribution between tracker A and B The connection of additional strings is possible These must be externally connected We recommend connecting further strings in...

Page 38: ...t fall below 150 VDC at maximum UMP performance or exceed 450 VDC Within one tracker only modules of the same type with the same power can be used Two strings can be connected with the ES4200 ES5000 m...

Page 39: ...rectly 5 Cover the unused sockets of the DC input with the supplied protective caps 6 Start up the photovoltaic solar inverter 5 2 3 Overview of cabling for the PV module 1 String A 2 String B 3 DC co...

Page 40: ...cabled on one string In the case of wiring with one string you must switch the operating mode in the configuration to parallel see Chapter 7 2 Country settings operating mode settings and ID settings...

Page 41: ...l ES series 41 6 Control Panel 1 LCD display 2 LED display 3 Operating keys Fig 6 1 Control panel 1 LCD display LINE Power source Service operation Solar cells Flow chart of the photovoltaic solar inv...

Page 42: ...r cells is less than 5 of the nominal performance of the photovoltaic solar inverter 3 Operating keys Confirm a change to the settings of the photovoltaic solar inverter Continue to next page or chang...

Page 43: ...ectrical components or equipment in accordance with electrotechnical rules 2 Safety Instructions Check the following points before you start up the photovoltaic solar inverter The housing is safely sc...

Page 44: ...voltage reaches 120 VDC All LEDs light up The following is shown on the LCD display Fig 7 1 1 Display A After 3 seconds the LCD display changes from Display A to Display B1 total feed power and Displa...

Page 45: ...erter switches to the mode Settings and you see the following display 2 Press the key to select the appropriate country settings dE Germany ES Spain It Italy Fr France bE Belgium Pt Portugal Gb Great...

Page 46: ...ssign an identification number ID no to your photovoltaic solar inverter in the range from 1 200 You need the ID number to be able to differentiate between different photovoltaic solar inverters in on...

Page 47: ...sary Set the AC circuit breaker to ON Wait 30 seconds legally required waiting period The LCD display changes between the Displays C1 total feed power and Display C2 alarm code The yellow LED lights u...

Page 48: ...f the photovoltaic solar inverter is working incorrectly e g short circuit an error code or the error status will appear on the display Fig 7 3 5 Display F A list of possible error codes with explanat...

Page 49: ...ugh the LCD display Use the and buttons to scroll the displays The measurement readings and numbers are shown in the following order when scrolling downwards Fig 7 4 1 Display G Total feed power Fig 7...

Page 50: ...ES Commissioning ES series 50 Fig 7 4 5 Display K Temperature of cooling element in F Fig 7 4 6 Display L String A voltage Fig 7 4 7 Display M String B voltage Fig 7 4 8 Display N String A current Fi...

Page 51: ...tring A output power Fig 7 4 11 Display Q String B output power Fig 7 4 12 Display R Output voltage of the photovoltaic solar inverter Fig 7 4 13 Display S Frequency of the photovoltaic solar inverter...

Page 52: ...ating state Display on the LCD display Explanation Normal The photovoltaic solar inverter is working normally When the delivered performance of the PV panel is sufficient 500 VDC PV 120 VDC it supplie...

Page 53: ...nctions such as mains problems or internal errors this is showed on the display and the red LED lights up EPO Emergency power off The photovoltaic solar inverter does not receive any power from the ma...

Page 54: ...ation interfaces are designed for this 8 1 Standard communication interface The standard communication interface for the photovoltaic solar inverter is an RS232 serial interface otherwise known as EIA...

Page 55: ...d technical details 8 3 Optional data cards If you need other interfaces than the standard communication interface you can install an optional communication card Data cards should only be plugged in w...

Page 56: ...ies 56 Fig 8 1 3 2 Data cable Insert the data cable through the cable inlet of the cover Fig 8 1 3 3 Connect the communication card Connect the data cable to the communication card Fig 8 1 3 4 Insert...

Page 57: ...d tighten the four screws evenly 8 3 2 RS485 card Fig 8 1 2 1 RS485 card CN1 is intended for the terminating resistor You can activate the function with pin 1 2 terminating resistor jumper ON you can...

Page 58: ...8 3 3 RS485 interface wiring DC Several photovoltaic solar inverters with Solar LogTM 1 Solar inverter address 1 2 Solar inverter address 2 3 Solar inverter address 3 4 Solar inverter address 4 5 Sol...

Page 59: ...s 59 2 Several photovoltaic solar inverters connected to a PC 1 Solar inverter address 1 2 Solar inverter address 2 3 Solar inverter address 3 4 Solar inverter address 4 5 PC 6 RS485 RS232 adapter 7 R...

Page 60: ...unication Interfaces ES series 60 DCI Connection to the RS485 card first photovoltaic solar inverter 1 Nothing should be connected here 2 4 core twisted pair screened cable Fig 8 3 3 3 Connect the RS4...

Page 61: ...able 7 Screen one sided to PE Fig 8 3 3 4 Connect the RS485 card several photovoltaic solar inverters In the case of several photovoltaic solar inverters the RS485 bus is looped through the individual...

Page 62: ...omunication Interfaces ES series 62 8 3 4 USB card Fig 8 3 4 1 USB card Definition Compatible USB version 1 0 1 5 MBit s Compatible HID Version 1 0 Pin assignment for the USB card 1 VCC 5 V 2 D 3 D 4...

Page 63: ...low the range 2 Pin 2 At least one DC input above the minimum limit 3 Pin 3 All DV input voltage below the minimum limit 4 Pin 4 Frequency of the AC output mains outside the tolerance 5 Pin 5 Isolated...

Page 64: ...load of max 40 VDC 25 mA You can switch the output signal from N C normal close to N O normal open by bridging Pin 1 and 2 or Pin 2 and 3 from JP1 5 with the jumpers 8 3 6 SNMP card Fig 8 3 6 1 SNMP c...

Page 65: ...osis system identifies a particular problem the appropriate service code is showed on the LCD display The following work may only be performed by trained technical staff 9 1 Error codes and explanatio...

Page 66: ...Er26 BOOSTER_B over current Er29 PV inverter output DC current over spec DC current at output of photovoltaic solar inverter is too high Er06 EPO The photovoltaic solar inverter is in emergency power...

Page 67: ...ccurs again please contact your dealer Er18 Heat sink over temperature The temperature on the cooling element is too high Er01 Ground fault The fault current has reached the authorised upper limit 12...

Page 68: ...quency The mains frequency is higher or lower than the authorised amount AL03 Utility Voltage Under Frequency AL04 BOOSTER_A Input Over Voltage Under or over voltage of the DC input 20 Disconnect all...

Page 69: ...d 29 If the error occurs again please contact your dealer AL10 GFDI The fault current of the grounding wire is too high 30 Disconnect the PV generator from the feed and check the peripheral AC system...

Page 70: ...s occur with the photovoltaic solar inverter or you need safety information please contact our service hotline Phone no 0049 0 741 17451 0 Fax no 0049 0 741 17451 29 If you cannot reach us by phone or...

Page 71: ...ker 14 6 A 22 A 2 x 14 A 2 x 17 65 A Max power per MPP tracker 2200 W 3300 W 2100 W 2650 W MPPT range 150 VDC to 450 VDC MPP tracker 1 2 Output data AC Nom AC power 2000 W 3000 W 4000 W 4600 W Max AC...

Page 72: ...sumption approx 1 W Environment Operating temperature 25 to 50 13 F to 122 F Humidity 0 to 90 without condensation Technology Dimensions H x W x D mm 430 x 455 x 190 510 x 455 x 190 Weight net 27 kg 2...

Page 73: ...solar cells is above or below 5 of the nominal performance of the photovoltaic solar inverter Operating keys Navigation keys function key enter key Safety Mains Over under voltage over under frequency...

Page 74: ...Photovoltaic Solar Inverter Series ES Technical Data ES series 74 11 2 ES2200 ES3300 Block diagram...

Page 75: ...Photovoltaic Solar Inverter Series ES Technical Data ES series 75 11 3 ES4200 ES5000 Block Diagram...

Page 76: ...View Article number 1 Photovoltaic solar inverter ES2200 SLWRABSI2K0Wx000 or ES3300 SLWRABSI3K0Wx000 or ES4200 SLWRABSI4K0Wx000 or ES5000 SLWRABSI5K0Wx000 X 1 Wall mounting Assembly plate for wall mou...

Page 77: ...assembly material Upon request X IP65 protection IP65 protection consists of Upon request X 2 covers Upon request X 2 washers Upon request X 8 screws Upon request X 1 DC circuit breaker SLDFKNMS32AWX...

Page 78: ...photovoltaic solar inverter SLZBSLDL21050100 Solar Log 500 up to 10 photovoltaic solar inverters SLZBSLDL21100100 Solar Log 1000 up to 100 photovoltaic solar inverters Further versions available on r...

Page 79: ...ce Relay plug in card Relay expansion card for photovoltaic solar inverter SLZBABEKRCBPX000 O SNMP WEB plug in card SNMP WEB expansion card for photovoltaic solar inverter SLZBABEKWEBPX000 O X include...

Page 80: ...Photovoltaic Solar Inverter Series ES Declaration of Conformity ES series 80 12 Declaration of Conformity...

Page 81: ...Photovoltaic Solar Inverter Series ES ES series 81 Notes...

Page 82: ...Photovoltaic Solar Inverter Series ES ES series 82 Notes...

Page 83: ...Photovoltaic Solar Inverter Series ES ES series 83 Notes...

Page 84: ...EFFEKTA Regeltechnik GmbH Rheinwaldstra e 34 D 78628 Rottweil Germany...

Reviews: