72
2.5.3
Overall terminal diagram 720-30 with terminal module 1370-10
ì
The control unit and
terminal module must be
connected via the cable
shields. However, these
must only be grounded on
one side (at the control
unit).
í
The shields of all
conductors occurring at
the control unit must be
connected here to the
grounding bar. They may
only be grounded on one
side.
î
Jumper J1
The sabotage contact of
the terminal module can
be set as a n.c. or n.o.
contact using jumper J1.
In the control unit 720-30
it must be set as a n.o.
contact.
For this reason, it must
be plugged over to
position 2-3. Note: The
status on delivery is
position 2-1!
rd gn ye
Terminal module 1370-10/11
Locking element
connection,
16 23
17 18 22 19 20 21 14 13
1 2 3 4 5 6
7 8 9 10 11 12
3
1
2
SK
J1
Loc
ked
Un
lo
ck
ed
Ala
rm
S
ab
ot
age cont
ac
t,
(s
w
itc
hi
ng
pos
ition:
li
d open
)
R
es
et
alar
m
/ unlo
ck
Lo
ck /
te
m
por
ar
y
re
lease
»
»
»
=
+
-
+
-
230 V / 50-60 Hz
L1 N PE
L1 N PE
1
2 3
4 5
6 7 8
9 10 11 12 13 14 15
Emergency exit control unit 720-30
Note:
When two locking elements
are connected to the control
unit (e.g. in the case of
two-leafed doors), both the door
contact and the locked status
monitors (armature contact /
Hall element) must be switched
.
in series
Battery charge voltage
(See operating instructions)
Mains voltage
B
atte
ry
12
V
, 2
A
H
B
atte
ry
12
V
, 2
A
H
5
6
4
3
2
5
6
4
3
2
A
B
D
E
F
C
Holding magnet
model 828, 24 V
Holding magnet
model 828, 24 V
Door
contact
Door
contact
F 1
0,5 AT
F 2
2 AT
F 3
1,25 AT
F 5
1,25 AT
F 6
1,25 AT
Setting range
Output voltage
24 V +10%
PO 1
PO 2
F 7
0,1 AT
AK 1
AK 2