Parameterization
Reporting sequence
Designation
Selection options
Note
Signaling
1-Frequency
1- Frequency flashing light
2-Frequency
2- Frequency flashing light
State display
Self-clearing alarm: Alarm is immediately displayed
as an acknowledged alarm and goes when the
associated input is no longer present.
Reporting
sequence
New value
New value alarm
First value
First value alarm
Steady light
Only selectable in conjunction with 2-frequency
Collective alarm
Input parallel static
The collective alarm is set with the first coming
alarm and goes, regardless of the
acknowledgement, with the last going alarm.
Input parallel static dynamic
The collective alarm is set with the first incoming
alarm. With each further alarm, the collective alarm
is deleted for approx. 0.8 s and then set again.
When all alarms have gone, the collective alarm is
permanently deleted.
Output parallel static
The collective alarm is set with the first incoming
alarm. The collective alarm is only deleted when all
alarms have been sent
and
acknowledged.
Output parallel static
dynamic
The collective alarm is set with the first coming
alarm. With each further alarm, the collective alarm
is deleted for approx. 0.8 s, then set again. When
all alarms have gone
and
have been
acknowledged, the collective alarm is permanently
deleted.
dynamic
The collective alarm is activated for approx. 0.8 s
with each incoming alarm.
Input parallel statically
acknowledgeable
The collective alarm is set with the first coming
alarm and goes with the last going alarm or when
all alarms have been acknowledged.
Output parallel statically
acknowledgeable
The collective alarm is set with an upcoming alarm.
When the alarm is acknowledged, the collective
alarm is deleted, even if alarms are still pending.
Horn control
Horn can be triggered again
The horn is activated again with the next alarm,
even if alarms are already pending.
Horn cannot be controlled
again
The horn is only activated again for subsequent
alarms if no alarms are pending.
Table 5.2: Dialog field reporting sequence
More detailed information on the reporting procedures and their designation can be found
in the separate document "Description of the reporting procedures" with the document
designation "SM-MA-ZI-UK".