MSM-USM2G-BA-UK-004
Table 3.2-1: Error code of the USM part 1
17
Operating voltage 1
This error can occur in annunciators with dual power supply.
18
Operating voltage 2
19
Configuration inconsistent
The downloaded configuration does not match the hardware of
the device (e.g. USM08 and USM16).
31
License error
The IEC 61850 license does not match the device. Has the right
license file been downloaded to the device? Please contact
customer service.
32
CID-file missing
Please download CID-file to the device.
33
Parameter file missing
Restore factory setting via web server, then perform
parameterization again or import. Contact customer service if the
error persists.
34
Imported configuration is
faulty
Download correct file to the device or restore default setting by
means of the web-server.
35
Faulty CID-file
The downloaded CID-file is incorrect. Please download the
correct CID-file to the device.
41
Extension address
incorrect
In cascaded systems
The slave generates the error when it is set to address "0".