CMDN Manual
15
[CMDN-011.CDR]
CMDN(-C) Flush Mount Enclosure
IRC-3 and FCC Field Wiring
The total length of the RS-485 communications loop used to connect
multiple annunciators cannot exceed 7,700 feet (2348 m). Wire
annunciators per the following figures.
Annunciator IRC-3 and FCC Terminal Connections
Terminal
Function
1
+ 24 Vdc
2
24 Vdc Common
3
Earth Ground
4
RS-232, Rx In
5
RS-232, Tx Out
6
RS-232, Common
7
RS-485, Ch 0 (+)
8
RS-485, Ch 0 (-)
9
RS-485, Ch 1 (+)
10
RS-485, Ch 1 (-)
Note:
For Style 4 (Class B) wiring, use only RS-485 Channel 0. For
Style 7 (Class A) wiring, use both RS-485 channels.
firealarmresources.com