Deutronic Elektronik GmbH
Deutronicstr. 5, D - 84166 Adlkofen
Tel.: +49 8707 920-0
Fax: +49 8707 1004
E-Mail: [email protected]
http://www.deutronic.com
D-IBM2900
Stand: 08.03.2022
Seite 12 von 25
Technical Data
D-IBM2900-3AC
Input
Input voltage range
320 – 550VAC
Protection class
I
Inrush current::
Inrush current impulse, actively controlled <= 70A +/- 10%
Power consumption during
full load
<10A (internal device fuse)
Transient
overvoltage
protection
EN60335
Input fuse
External 3 pole LS switch 16A, preconnect characteristic B
Idle power (Stand-by):
<60 Watt
The AC/DC converters feature Power Factor Correction current
limiting
Output
Output voltage:
Battery operation: 410 - 550VDC
Mains operation: 430 - 740VDC (rectifier voltage from bypass)
Nominal voltage: 460VDC
Length of the output line:
2 m
Output safety circuit fuse
1000VDC 6A IEC60269-4
Overall efficiency
>77%
Operating Conditions
Industrial environment
Mechanical Data/ Environmental Influences
Protection class:
IP20
Operation temperatures:
0 to +45°C
Environment temperature:
0 to +45°C
Storage temperature:
-10 to + 45°C
Cooling:
Active, with fan
Rel. humidity
5 to 95% humidity, non-condensing
Isolation voltage:
1000 VDC of all inputs and outputs against PE
Housing:
Plastic and aluminum
Dimensions:
Ca. 450x550x170 mm