System
SpecificationsError! Reference source
not found. A-1
A p p e n d i x
A
A
p
p
e
n
d
ix
A
System Specifications
This appendix covers the basic specifications of the meter.
Measured Quantities and Methods
The meter can measure the quantities listed in Table A-1.
Quantity Units Description
Watt hours
Wh
The total Wh.
var hours
Varh
The fundamental varh.
In 2 element mode calculated from sqrt(VAh
2
- Wh
2
)
VA hours
VAh
The total VAh, calculated from Vrms x Irms.
In 2 element mode calculated from sqrt(Wh
2
+ varh
2
)
Watts
W
The total W.
vars
Var
The fundamental vars.
In 2 element mode calculated from sqrt(VA
2
- W
2
)
VA
VA
The total VA, calculated from Vrms x Irms.
In 2 element mode calculated from sqrt(W
2
+ var
2
)
Voltage
V
True RMS voltage.
Current
A
True RMS current.
Frequency
Hz
Fundamental system frequency.
Phase Angle
Degrees
Angle between Fundamental Voltage and Fundamental Current.
Phase to
Phase Angle
Degrees
Angle between Fundamental Voltages.
Power
Factor
Ratio
Watts divided by VA. Lead or lag determines the sign.
•
Table A-1 Measurements