background image

INTERFACE BOARDS

Company:

Device:  

Document: 

Code:

Date:

Page:

Ediseja 21 STR 100

User manual STRMUED1

09.08.2019

17

Picture 14: Use „IP Configuration/Use the following IP configuration:“ settings and set IP according to your

needs.

Picture 15: Set as shown on both STR devices

Summary of Contents for STR 100

Page 1: ...STR 100 Company Device Document Code Date Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 STR 100 Signal Transducer User manual ...

Page 2: ...2 RS485 INTERFACE BOARD 11 4 2 3 VERSATILE LINK FIBER OPTIC INTERFACE BOARD 13 4 2 4 MULTIMODE FIBER OPTIC INTERFACE BOARD 14 4 2 5 SINGLEMODE FIBER OPTIC INTERFACE BOARD 14 4 2 6 10 100BASE TX ETHERNET INTERFACE BOARD 15 4 2 6 1 LANTRONIX INSTALLER SETTINGS 16 4 3 IO BOARDS 21 5 SCHEMATIC 26 5 1 STR 100 x x NON IOx 26 5 2 STR 100 x x NON IOxR 27 6 TYPICAL CONNECTION 28 7 INSTALLATION 29 7 1 INSTA...

Page 3: ...ISSIONING MAINTENACE 31 8 1 COMMISSIONING 31 8 2 MAINTENANCE 31 9 TECHNICAL DATA 32 10 DIMENSIONS 37 11 ORDERING 38 Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 3 ...

Page 4: ... d o o Drenov Gric 175 1360 Vrhnika Slovenia EU Tel 00 386 51 643 411 051 643 411 Email grega flander ediseja21 com www ediseja21 com Copyright Copyright Ediseja 21 2013 All rights reserved Explanation of the symbols Read the instructions Device was tested with 2 5 kV AC voltage to check the device insulation Device ground terminal Waste Electrical and Electronic Equipment WEEE Directive 2002 96 E...

Page 5: ...eration Disregarding of safety rules can result in severe personal injury or property damage Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations Warning Device must operate completely assembled Device must be used as described No modifications of the device should be made Warning Do not open devic...

Page 6: ...cted BAUD rate 4 digital inputs 4 dIgital outputs DIN 35 rail mount Short response time 2 3 FUNCTION Two devices from STR 100 system works in pair Input statuses from one device are transfered to second device outputs and vice versa Devices are coupled through full duplex commnication link Communication is based on special protocol If communication link is broken DO statuses of both devices are re...

Page 7: ...es power supply voltage others indicate communication and IOs activity 2 4 TYPICAL APPLICATION Typical application is transfer of trip command and circuit breaker status between two substations 2 5 CONSTRUCTION Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 7 Picture 2 STR 100 typical application ...

Page 8: ...rnet board IO board IOL 4 Digital Input 24 V DC 4 Digital Output board IO4 4 Digital Input 48 V DC 4 Digital Output board IO1 4 Digital Input 110 V DC 4 Digital Output board IO2 4 Digital Input 220 V DC 4 Digital Output board User can order any combination that suits him or her best 2 6 HOUSING Housing of STR 100 system devices is aluminium and intended for mount on standard DIN 35 rail acc to DIN...

Page 9: ... types of device are same except communication interface connectors are different Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 9 Picture 3 STR 100 x 232 NON x front view left bottom view right ...

Page 10: ...Phoenix MSTB 1 2 Description L N L L1 For further technical data see chapter TECHNICAL DATA 4 2 INTERFACE BOARDS User can choose between following interface boards RS232 board RS485 board Versatile link plastic fiber optic board Multimode Fiber Optic ST connector board Singlemode Fiber Optic SC connector board Singlemode Fiber Optic FC connector board Singlemode Fiber Optic ST connector board Ethe...

Page 11: ...vice to work properly demands that RS485 must always be in known and valid state That is when positive pin is more than 200 mV positive than negative pin Pins and are sometimes marked as A and B In case that no device on RS485 bus is transmitting or in case of short circuit there is no voltage difference between those pins and some device do not work correctly On this port board so called true fai...

Page 12: ...gs If special protocols small request respond time required are used please note it in order NOTE If there are problems with communication try using higher speed setting Some manufacturer have different markings for B and A line Try to switch A and B wires See http en wikipedia org wiki RS 485 for detailed information Connector pin table MSTB 1 2 3 Description GND A B Page Company Device Document ...

Page 13: ...40 kbit s Hardware settings For proper functioning of that port optic logic must be set the same on both devices that communicates Fiber optic logic settings Switch SW1 Light in idle state 1 2 3 4 Positive logic OFF OFF ON OFF ON Negative logic ON ON OFF ON OFF Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 13 Picture 7 Data rate vs cable lenght Picture 8...

Page 14: ... Description Full duplex singlemode 1310 nm up to 2 048 Mbit s fiber optic port with SC connectors interface FOS FC connectors interface FOF or ST connectors interface FOU This interface allows transmission up to 20 km Signal detect LED is activated when receiver receives enough light signal from transmitter from another end of the fiber cable Warning Radiation emitted by single mode laser devices...

Page 15: ...rminated LED functions Upper LED Link Lower LED Activity Description Meaning BAUD rate selection BAUD rate selection Off No Link Off No Activity Amber 10 Mbps Amber Half Duplex Green 100 Mbps Green Full Duplex Software setting For using this interface Installer program is needed It can be obtained from www ediseja21 com STR100 4channel signal transucer htm Installer program is needed for setting I...

Page 16: ...e Document Code Date 16 Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 Picture 13 Press Ok Picture 11 Start program and press Search to find device then select device to be set press icon Assign IP type request IP number and press button Assign Picture 12 Press Web Configuration ...

Page 17: ... Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 17 Picture 14 Use IP Configuration Use the following IP configuration settings and set IP according to your needs Picture 15 Set as shown on both STR devices ...

Page 18: ...0 Signal Transducer Page Company Device Document Code Date 18 Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 Picture 17 Serial Settings on both STR devices Picture 16 Hostlist settings on both STR devices ...

Page 19: ...Settings Data Bits 8 Port Settings Parity Even Port Settings Stop Bits 1 Pack Control Enable Packing checked Pack Control Idle Gap Time 12 ms NOTE This are default factory settings Do not change any of this settings otherwise device can stop working correctly Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 19 ...

Page 20: ...ndpoint Configuration Local Port 10001 10001 Endpoint Configuration Remote Port 10001 10001 Endpoint Configuration Auto Increment Local unchecked unchecked NOTE This are default factory settings Do not change any of this settings otherwise device can Page Company Device Document Code Date 20 Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 Picture 18 Connection Settings ...

Page 21: ...l Digital inputs are scaned every 0 1 ms Debounce filter is 20 That means that digital input will be recognized as active if in all 20 cycles status of digital input will be high Digital outputs 1 3 are controlled by communication After positive command request requested digital output will be activated for 500 ms After that time digital output will be automaticly returned to its initial state Dig...

Page 22: ...DO3 Normally Close contact pin 8 potential free DO3 Common pin 9 potential free DO3 Normally Open contact pin 10 potential free DO4 Normally Open contact pin 11 potential free DO4 Normally Open contact pin 12 DI1 input 13 DI2 input 14 DI3 input 15 DI4 input 16 DIs common GND Difference between IOx and IOxR board is in operation of first DO DO1 Page Company Device Document Code Date 22 Ediseja 21 S...

Page 23: ...vated If communication is not established DO2 is in its initial position Function of DO2 is set by switch 6 at the bottom of device LEDs operation LED ready signalize when device normaly operates If power is on and green LED ready blinks or does not light device does not operate correctly lights device operates normally Switches at the bottom of the device valid EXCEPT for STR 100 x ETH x x Switch...

Page 24: ...TH x x devices only Switch 1 2 3 4 Description communication fail delay delay ms Position OFF OFF OFF OFF 100 ON OFF OFF OFF 200 OFF ON OFF OFF 400 ON ON OFF OFF 800 OFF OFF ON OFF 1000 ON OFF ON OFF 2000 OFF ON ON OFF 4000 Default position ON ON OFF OFF It is recommended that settings of time delay is the same on both devices working in pair Settings do not affect actual transmitting time It only...

Page 25: ... If change during operation is made disconnect power supply for a few moments until power LED stops emitting and connect power supply back New settings are then accepted On the bottom side of device are switches for device setting and ISP connector which is intended for upgradeing software Do not connect anything to that connector For further technical data see chapter TECHNICAL DATA Company Devic...

Page 26: ...utput On second picture DO1 works as ready indicator For further details see chapter HARDWARE DESCRIPTION IO BOARDS 5 1 STR 100 x x NON IOx x means any type for types description see chapter Ordering Page Company Device Document Code Date 26 Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 Picture 21 STR 100 x x NON IOx schematic ...

Page 27: ...STR 100 x x NON IOxR 5 2 STR 100 x x NON IOxR Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 27 Picture 22 STR 100 x x NON IOxR schematic ...

Page 28: ...STR 100 Signal Transducer 6 TYPICAL CONNECTION Page Company Device Document Code Date 28 Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 Picture 23 STR 100 x FOT NON IOxR typical connection ...

Page 29: ...ble operating temperature must be observed Check the device for damage at unpacking If device is damaged it must not be installed but it should be send to the manufacturer for repair The device should not be opened The device should be mounted on a 35 mm rail acc to EN 50022 Attach ground wire before attaching power supply Device must be grounded during operation Single core or stranded wire 0 5 2...

Page 30: ...y once after power up If change during operation is made disconnect power supply for a few moments until power LED stops emitting and connect power supply back Settings are then accepted For further details see chapter HARDWARE DESCRIPTION Page Company Device Document Code Date 30 Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 Picture 24 left installation right deinstallation ...

Page 31: ...No modifications of the device should be made Attach ground wire before attaching power supply Device must be grounded during operation Check if the power supply voltage complies with device operation voltage Do not open device while it is energized Hazardous voltage is present inside the device If device is equipped with singlemode fiber optic interface Warning Radiation emitted by single mode la...

Page 32: ... type MSTB Phoenix 2pin Power Supply Wire crossection 0 5 2 5 mm2 type single or stranded wire voltage rating 500 V colour see valid standard Ground wire crossection Cu 2 5 mm2 colour see valid standard Communication port RS232 interface type 232 Type RS232 Direction full duplex Speed up to 230 k BAUD Number of ports 1 Distance up to 15 m Isolation none GND earthed Connector type DB9 female Lines ...

Page 33: ...r Laser class I IEC 60825 1 eye safe Direction full duplex Speed up to 40 kbit s Input 1 receiver grey connector Output 1 transmitter black connector Logic light OFF positive logic or light ON negative logic in idle state set by manual switch see table Distance up to 100 m Connector type Communication port Multimode Fiber Optic interface type FOT Type multimode fiber optic Wave lenght 820 nm Fiber...

Page 34: ...ut power 7 to 0 dBm Reciver sensitivity 18 dBm Receiver overload 7 dBm Laser class I IEC 60825 1 Direction full duplex Speed up to 115200 BAUD Input 1 receiver Output 1 transmitter Distance up to 20 km Connector type CMU 100 x x FOS SC CMU 100 x x FOF FC CMU 100 x x FOU ST Communication port 10 100BASE TX interface type ETH Type ethernet Direction full duplex Speed 57600 BAUD Manufacturer Lantroni...

Page 35: ...den 0 35 A at 220 V resistive bourden Connector type screw type MSTB Phoenix 16 pin Wire crossection 0 5 2 5 mm2 type single or stranded wire voltage rating 500 V colour see valid standard Communication speed vs transmission time Transition time 1200 BAUD 110 ms 2400 BAUD 61 ms 4800 BAUD 34 ms 9600 BAUD 20 ms 14400 BAUD 14 ms 19200 BAUD 13 ms 38400 BAUD 10 ms 57600 BAUD 9 ms 76800 BAUD 8 ms 115200...

Page 36: ... Humidity operating up to 95 noncondensing Enclosure Material Al IP 20 Mount type standard DIN 35 rail acc to DIN EN 50022 35 Class I Overvoltage category II Communication indicator Receiveing yellow LED marked Rx Tranmitting green LED marked Tx Page Company Device Document Code Date 36 Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 ...

Page 37: ...DIMENSIONS 10 DIMENSIONS Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 37 Picture 25 Dimensions ...

Page 38: ...ic with FC connector 20 km FOF Singlemode 1310 nm fiber optic with ST connector 20 km FOU 10 100Base Tx Ethernet ETH Digital input output 4 DI 24 V DC 4 DO 250 V AC 5 A IOL 4 DI 48 V DC 4 DO 250 V AC 5 A IO4 4 DI 110 V DC 4 DO 250 V AC 5 A IO1 4 DI 220 V DC 4 DO 250 V AC 5 A IO2 4 DI 24 V DC 3 1 ready DO 250 V AC 5 A IOLR 4 DI 48 V DC 3 1 ready DO 250 V AC 5 A IO4R 4 DI 110 V DC 3 1 ready DO 250 V...

Page 39: ...eja 21 d o o Stegne 21C 1000 Ljubljana Slovenia EU Tel 00 386 51 643 411 051 643 411 grega flander ediseja21 com www ediseja21 com Company Device Document Code Date Page Ediseja 21 STR 100 User manual STRMUED1 09 08 2019 39 ...

Reviews: