INSTALLATION INSTRUCTIONS

Smoke channel

The conduit which connects the hearth
smoke outlet mouth with the flue inlet is
called smoke channel.
The smoke channel must be made with
stiff steel or ceramic pipes, flexible
metal or fibre-cement pipes are not allo-
wed.
Horizontal or counterslope tracts must
be avoided.
Eventual section changes are allowed
only at the chimney outlet and not, for
example, at the coupling in the flue.
Slants of more than 45° are not allowed.
A mastic sealing at high temperature
must be carried out in correspondence of
the inlet point of the steel flue on the
chimney smoke outlet mouth.

Further to the above, bear in mind the
indication of the UNI 10683 rule in
paragraph 4.2 „connection to the
smoke evacuation system“ and sub-
paragraphs.

the max. ratio between the sides must
not exceed 1.5
- have an internal section with a surface
at least equal to the one reported on the
technical board
- service only one hearth (chimney or
stove).
Piping using stainless steel pipes of appro-
priate size and ideal insulation is sugge-
sted for flues which are old or too large.

In the event of a chimney with length
of 5 meters is necessary to install a
flue damper control.

The chimney pot fundamental featu-
res are:

- basic internal section equal to the one
of the flue
- outlet section not less than double that
of the flue
- position in full wind, above the roof
and outside the reflux areas.

Fireplace 

If combining a prefabricated Edilkamin
covering, to decide upon the exact posi-
tioning of the fireplace, it is important
to verify which covering will be pplied.
The positioning is implemented accor-
ding to the model chosen (refer to the
installation instructions found inside the
packaging of each fireplace covering).
Always ensure the fireplace is level
during the installation process.
- Drill a hole into the wall or the floo-
ring for the external air intake and con-
nect the air adjustment mechanism to
the hole as described in the chapter cal-
led “external air inlet”.
- Use a stainless steel flue to connect
the fireplace to the chimney flue, adhe-
ring with the diameters indicated in the
specifications table (page. 14) and the
guidelines given in the chapter called
“chimney flues” (page. 16).
-  kits are available for channelling hot
air as described in detail on page 17.
- once installation is complete, enable
the sliding of the door by moving the
two levers, 

X

and 

X1

, towards the door

(fig. 

H

I

pg. 18)

- ensure that the parts work when they
are handled.

Coverings, fireplace mantels and their
vents (fig. 1) 

Before installing the covering 

make sure

that the connections

, control levers and

all moving parts are functioning correc-
tly. 

These checks must be performed

when the fireplace is lit 

and has been

running for a few hours, before covering
the firebox, so that it is still possible to
intervene if necessary Therefore, the fini-
shing operations such as:

- building the fireplace mantel
- installing the covering
- implementing pilasters, painting, etc..
should be performed after tests provides
successful outcomes.
Edilkamin will not be held responsible
for costs deriving from demolition or
reconstruction work even they result
from the replacement of any parts of the
firebox that have been found to be
defective. 
Marble, stone, and brick parts that make
up the covering must be installed lea-
ving a slight gap between the pre-fab in
order to avoid possible breakage due to
dilation and excessive overheating.
In particular, you must include the follo-
wing below the edging of the bottom
edge:
- a space suitable enough to allow the
recirculation of air from the room to
flow through
- the possibility of inspecting and or
replacing the fans in the case of firebo-
xes with forced ventilation.
Wooden parts must be protected by fire
resistant panels and no part must touch
the thermo fireplace, on the contrary,
there must be an appropriate distance of
at least 1 cm to allow the air to flow, pre-
venting heat accumulation. The fireplace
mantel can be made of fireproof plaster-
board panels or gypsum board; during
the construction phase the hot air chan-
nelling kit must be mounted as stated
above. Air should be allowed to flow
inside the fireplace mantel (through the
gap between the door and the beam).
Through convective motion, the air will
flow out from the grille installed at the
top, resulting in heat recovery and pre-
venting excessive overheating.

In addition to the above, please consi-
der the indications stipulated in the
UNI 10683 standard, paragraphs 4.4
and 4.7: insulation, finishing, fireplace
covering and safety recommenda-
tions.

Flue and chimney pot

The conduit which, from the room with
the chimney reaches the building cove-
ring, is called flue.

The fundamental features of the flue
are:

- capability to support a smoke tempe-
rature of at least 450°C with regard to
the mechanical resistance, insulation,
and gas hold
- being correctly insulated to avoid the
forming of condensation
- have constant section, almost vertical
flow and not slant more than 45°
- have preferably circular internal sec-
tions; in case of rectangular sections,

fig. 1

hot air flow
grille

fireplace 
mantel

sliding door rails

metallic shell

hood

wooden
beam

front panel

sliding door

Summary of Contents for 809490

Page 1: ...TITANO UP2 UK Installation use and maintenance ...

Page 2: ...all relieve the manufacturer from any damage resulting from the use of this product the proof of purchase tag necessary for identifying the fireplace is located on the top of the package in the warranty booklet found inside the firebox on the ID plate affixed to the back side of the unit This documentation must be saved for identification together with the valid proof of purchase receipt The data ...

Page 3: ...ure MANIGLIA ASPORTABILE PER APERTURA PORTELLONE The handle of the hatch is not fixed to the same hatch but is inserted when required The handle fits into the bottom of the door by hooking it onto the pins The handle is only needed to lift or lower the hatch BUILT IN SYNOPTIC PANEL for models with forced ventilation it allows you to manage and control the operating phases ignition and turning off ...

Page 4: ... controlled mechanism recessed in the bottom front panel of the firebox When the fireplace is operating control lever 1b must be par tially or fully positioned to the right room outside air fitting 4b the sensor cables and the 230 Vac power supply can be positioned independently either to the left or to the right hot air outlet SPECIFICATIONS 4b 4b 1b A C hot air outlet pipes 230 Vac power supply ...

Page 5: ...type of surfaces present and how they are made Hot air outlets Grillsr The hot air outlets must be placed at a minimum distance of 50 cm from the ceiling and 30 cm from the furniture Position the grills or the air outlets at the highest point of the covering in order to avoid heat accumulating insi de the same covering Position the grills or the air outlets so that they can be easily accessed for ...

Page 6: ...place mantels and their vents fig 1 Before installing the covering make sure that the connections control levers and all moving parts are functioning correc tly These checks must be performed when the fireplace is lit and has been running for a few hours before covering the firebox so that it is still possible to intervene if necessary Therefore the fini shing operations such as building the firep...

Page 7: ...hem with their clamps build the frame with the fitting for outlet B1 into the wall on the top part of the fireplace mantel build the frame with the fitting for outlet B3 into the wall of the room requiring heating connect the two aluminium pipes to the fittings and secure them with clamps and snap on the front grilles Kit Three bis for the room where the fireplace is installed plus two adjacent ro...

Page 8: ...orting the fireplace In order to facilitate transportation the fireplace can be made lighter by remo ving the following counter weights cast iron bottom cast iron sides cast iron hearth the ash pan the ash grill made of cast iron the outer shell Dismantling the door Phase 1 fig H I lower the door to the fully closed position move levers X and X1 towards their respective jambs Phase 2 fig L open th...

Page 9: ...5 cm secure the sensor 14 inside the hole 22a of the outlet B1 or B3 check that the wire of the sensor does not interfere with the movement of the retractable door the second side panel finish the mantel by mounting the second side panel and apply the snap on grilles to the outlets from the outside when the work is complete plug in the plug to the 230 Vac power supply ensure that the electrical wi...

Page 10: ...stalled on the mantel of the covering When the fan is off the fireplace runs on natural convection Operating on forced ventilation in Automatic The fan is connected to a sensor moun ted on the hot air outlet on the mantel which starts up automatically once it reaches a temperature of 40 C and stops again automatically when the temperatu re drops below 40 C Manual The fan begins operating regardles...

Page 11: ...liquid fuel such as petrol alcohol or similar Do not burn waste Radiation field Do not place any fuel object inside the radia tion field of the glass hatch Initial start up The paint of the hearth is subject to the so cal led ageing until the working temperature is reached for the first time This may cause unpleasant odours In such case adequately air the room where the hearth is installed The phe...

Page 12: ...rafusado é o painel de fundo 2a as partes laterais 2b 2c devem ser simple smente colocadas em posição atenção permanecem instáveis até a montagem do painel de fundo 2a parte lateral anterior esquerda 2c parte lateral posterior esquerda 2b parte lateral posterior direita 2b painel de fundo com guarnição 2a desparafusar os dois parafusos inseridos na parte inferior da estrutura realizada com chapas ...

Page 13: ...n 2 viti 2 screws 2 tornillos 2 parafusos 2 βίδες 2 винта sk tecnica multi MONTAGGIO GHISE TITANO PLUS Layout 1 24 05 2012 16 59 Pagina 2 ...

Page 14: ...rafusado é o painel de fundo 2a as partes laterais 2b 2c devem ser simple smente colocadas em posição atenção permanecem instáveis até a montagem do painel de fundo 2a parte lateral anterior direita 2c parte lateral posterior direita 2b parte lateral posterior esquerda 2b painel de fundo com guarnição 2a desparafusar os dois parafusos inseridos na parte inferior da estrutura realizada com chapas m...

Page 15: ...n 2 viti 2 screws 2 tornillos 2 parafusos 2 βίδες 2 винта sk tecnica multi MONTAGGIO GHISE TITANO PLUS Layout 1 24 05 2012 16 59 Pagina 4 ...

Page 16: ...942074 GB 04 19 A w w w e d i l k a m i n c o m ...

Reviews: