CMUip-2212 Cabinet Monitor Unit
Operations Manual
Eberle Design Inc.
Page 20
The Datakey can be removed without the CMUip-2212 placing the cabinet into flash only if
the Front Door is Open.
When a Datakey is removed while the power is applied to the CMU-2212, the CMUip-2212
will continue to use the parameters from the removed Datakey until Reset is applied, a new
Datakey is installed, or a power-up cycle occurs. If a CMUip-2212 is Reset or powered-up
with the Front Door in the open position without a Datakey installed or with an invalid
Datakey, the CMUip-2212 will assume a default Datakey configuration according to the
Datakey Protocol Version.