2018KCL SERIES SIGNAL MONITOR
OPERATIONS MANUAL
Eberle Design Inc.
Page 37
170
Monitor DB-9
RX pin L
connect to
TX pin 2
TX pin K
connect to
RX pin 3
GND pin N
connect to
GND pin 5
DCD pin H should be connected to +5 pin D on the Controller Unit connector.
CTS pin M should be connected to RTS pin J on the Controller Unit connector.
9.5 ETHERNET LAN PORT
The Ethernet port must be configured with specific network parameters such as an IP
address. The network port parameters are set or changed using the EDI
ECcom
Signal
Monitor Communications software. See the "
EDI ECcom Software Operations Manual
"
for details on the SETUP / COMM PORT / SETTINGS /
Search
function.
The network port parameters can also be configured in the Datakey. See the
EDI ECcom
Operation Manual
(pn 888-1000-001) and
MonitorKey Operations Manual
(pn 888-
1212-001) for details.
The default network settings are:
IP Address
192.168.1.100
Subnet Mask 255.255.255.0
Gateway
none
9.5.1 ETHERNET LAN CABLE
The LAN cable required is a typical Cat-5 network cable using the 8 pin RJ-45 connector. If
the connection is from the monitor to a switch or hub, a standard LAN cable is needed. If
the connection is from the monitor directly to a network adaptor (PC), a cross-over or patch
cable is needed.