Page 24
4.2.3.4 MONITOR ID NUMBER
A monitor ID number can be set in the range of 0 to 99999999. This ID number is used
when retrieving event logs from the 2018KCL.
4.2.3.5 MONITOR ID NAME
A forty character monitor ID name can be set. This ID name is used when retrieving event
logs from the 2018KCL.
4.2.3.6 ONE SECOND WDT TIMING
If this option is selected, the WDT fault time is set to 1000 ms. See section 1.2.4.
4.2.3.7 WDT CLEAR ON PU
If this option is selected, either a Reset OR a power-up will clear a WDT fault (Caltrans
mode). The WDT fault is set to the latched mode by default. See section 1.2.4.1.
4.2.3.8 RED CABLE FAULT ENABLE
If this option is selected, the 2018KCL will enter the fault mode if the Red Interface cable is
not connected. See section 2.2.1.
4.2.3.9 RECURRENT PULSE DISABLE
The Recurrent Pulse Detection function is
DISABLED
by setting this option. See section
4.2.3.10 SPECIAL FUNCTION #1 INVERT
This option will invert the polarity of the Special Function input #1. See section 4.1.2.
4.2.3.11 RED FAIL TIMING SHORT
Selecting this option will extend the Red Fail fault timing to the 700-1000 ms value. 2.2
4.2.3.12 LEDGUARD
®
THRESHOLDS
Selecting this option will enable the LEDguard
®
thresholds. See section 2.6.
4.2.3.13 DUAL INDICATION TIMING LONG
Selecting this option will extend the Dual Indication fault timing to the 700-1000 ms value.
See section 2.3.
4.2.3.14 92VRMS BROWNOUT
Selecting this option will set the AC Line dropout and restore voltage and timing values to
the low (210E) settings in section 8.1.4. This option is intended for downward compatibility
with 210 monitor specifications. See section 2.5.
4.2.3.15 MC COIL INVERT
Setting this option will invert the polarity of the pin #EE (MC Coil) input. For a cabinet that
operates with the Flash Transfer relays de-energized for tri-color signal operation
(Caltrans), this option should not be selected. For a cabinet that operates with the Flash
Transfer relays energized for tri-color signal operation (Nema), this option should be
selected.
4.2.3.16 CONFIGURATION CHANGE FAULT
Selecting this option will enable the Configuration Change Fault mode. See section 2.11.