2010ECL-NYC SERIES SIGNAL MONITOR
OPERATIONS MANUAL
Eberle Design Inc.
Page 22
4.4.7 RF SSM SWITCH
Switch #7 of SW3 is labeled "RF SSM". When this switch is in the ON position, then each
channel will be monitored for a Red Fail condition if the corresponding SSM switch is in the
On position. See Section 2.2.1.
4.4.8 FYA MODE SWITCH
Switch #8 of SW3 is labeled "FYA Compact". When this switch is in the ON position, then the
Flashing Yellow Arrow monitoring mode is selected as FYAC Mode as described in Section
2.20.2 or 2.20.3. When this switch is in the OFF position, then the Flashing Yellow Arrow
monitoring mode is selected as FYA Mode as described in Section 2.20.1.
The FYA or FYAC monitoring mode is only active if one or more FYA channel pairs are
enabled with Option switches #8, 9, 10, or 11 described in Section 4.4.8.1.
4.4.8.1 FYA CHANNEL PAIR ENABLE SWITCHES
To enable a channel pair for FY
A operation, place the Option DIP Switch labeled “FYA x”
(where “x” is 1, 2, 3, or 4) in the On position. See Sections 2.20.1.2 and 2.20.2.2 and 2.20.3.
4.5 SELECT JUMPER PROGRAMMING
The Signal Monitor also provides jumper options to modify the monitor operation. The Select
jumpers are labeled SEL1 through SEL16. SEL6 through SEL16 are reserved for EDI
configuration programming and should not be modified except by the factory.
4.5.1 WATCHDOG LATCH SELECT (SEL1)
The WDT Latch select determines whether the WDT Error fault mode is latched through an
AC Line brownout or not. If the WDT Latch select is not jumpered, an AC Line brownout
condition will reset the WDT ERROR fault mode when the AC Line is restored. The WDT
Error indicator will remain illuminated until a Reset command is issued via the front panel
RESET button or External Reset input. See Section 1.2.3.
If the WDT LATCH select is jumpered, the WDT Error fault mode is maintained until a Reset
command is applied.
4.5.2 MINIMUM FLASH ENABLE SELECT (SEL2)
When jumpered, the Minimum Flash function provides a flash interval of at least 6 seconds
and at most 10 seconds in duration following a power-up, an AC Line interruption, or a
brownout restore. See Section 2.5.1.
4.5.3 CONFIGURATION CHANGE FAULT SELECT (SEL3)
When jumpered, the Configuration Change Fault function will be enabled causing the Signal
Monitor to enter the fault mode if any configuration parameter is changed. If the Configuration
Change Fault Select jumper is not installed, the unit will not set the fault mode but will log the
change event. See Section 2.11.
4.5.4 RED INTERFACE CABLE FAULT SELECT (SEL4)
When jumpered, the Red Cable Fault function will be enabled causing the Signal Monitor to
enter the fault mode if the Red Interface cable is not connected. If the Red Cable Fault Select
jumper is not installed, the unit will operate as a standard 210 monitor when the Red Interface
cable is removed. See Section 4.1.
4.5.5 AC LINE BROWN-OUT SELECT (SEL5)
When jumpered, the AC Line Brown-out levels will be set for the 2010 series with Dropout at
91 +
_2 Vrms and Restore at 94 +
_2 Vrms with timing at 450 +
_50 ms. When not jumpered, the