background image

2010ECL-NYC SERIES SIGNAL MONITOR 

OPERATIONS MANUAL 

Eberle Design Inc. 

Page 5 

A Clearance (short or absent Yellow) fault condition will place the Signal Monitor into the fault 
mode causing the Output relay contacts to close and enabling the Stop-Time output to the 
controller. This occurs when a Red input signal to a channel is active following the termination 
of an active Yellow input signal which is less than the minimum duration, including zero (i.e. 
skipped). 

2.5 AC LINE BROWN-OUT DETECTION 

When the AC Line voltage is below the "drop-out" level the Signal Monitor will suspend all 
fault monitoring functions, close the Output relay contacts, and enable the Stop-Time output 
to the controller. The AC POWER indicator on the front panel will flash at a rate of 2Hz to 
indicate the brown-out status.  When the AC Line voltage returns above the "restore" level 
the monitor will resume normal operation and the AC POWER indicator on the front panel 
will remain illuminated. 

The AC Brownout dropout and restore voltage levels are selected by the AC Line Brown-out 
Select jumper labeled SEL5. See Section 4.5.5. 

AC Line Brown-out Detection is provided to prevent a dark intersection in the event a brown-
out causes the cabinet controller to release control of the intersection. If this occurs and the 
intersection is not placed into flash, the monitor will detect a Red Failure (absence of signal) 
or  WDT  Error  and  will  require  a  manual  reset. 

The "low  AC  Line  Voltage"  level  on  the 

Controller Unit should be set at least 5 volts below the monitor drop-out level.

 

2.5.1 MINIMUM FLASH TIME 

A  Minimum  Flash  time  option  can  be  selected  (see  Section  4.5.2)  which  provides  a  flash 
interval of at least 6 seconds and at most 10 seconds in duration following a power-up, an 
AC Line interruption, or a brownout restore. During this interval the unit will suspend all fault 
monitoring functions and close the Output relay contacts.  The AC indicator on the front panel 
will flash at a rate of 4Hz. 

The minimum flash interval will be terminated after at least 6 seconds if the Watchdog input 
has made 5 transitions between the True and False state and the AC Line voltage is greater 
than the restore level. 

2.6 

LEDGUARD

®

 

LED FIELD SIGNAL SENSING 

The Signal Monitor can be configured to use a technique called 

LEDguard

®

 that is designed 

to  better  monitor  the  characteristics  of  LED  based  signal  loads  (See  Section  4.4.6).  Each 
field  signal  input  is measured  and compared to  both  a  high threshold and  a  low  threshold 
value to determine On / Off status. This differs from conventional operation where the active 
threshold is picked according to the color of the field signal. Once the high and low On / Off 
thresholds (Section 8.1.2) have been determined using the input RMS voltage, the individual 
fault monitor functions use the appropriate threshold to determine if a fault condition exists. 

 

LEDguard

®

 

Green/Walk

 

Yellow

 

Red/Dont Walk

 

Conflict

 

Low

 

Low

 

---

 

Red Fail

 

High

 

High

 

High

 

Dual Indication

 

Low

 

Low

 

Low

 

Clearance

 

Low

 

Low

 

High

 

2.7 RECURRENT PULSE DETECTION 

This error detection function supplements the normal Conflict, Dual Indication, and Red Fail 
monitoring algorithms for sensing faults that are intermittent or pulsing in nature.  The RMS-
Engine is designed to filter out short term transients commonly found on the electrical service 
and provide noise immunity against false signal detections.  The Recurrent Pulse detection 

Summary of Contents for 2010ECL-NYC

Page 1: ...2010ECLip 2018ECL 2018ECLip Firmware version 16AL43xx REVISION AUGUST 2019 pn 888 2010 115 MODEL 2010ECL NYC RMS Signal Monitor Operations Manual NOTE EDI ECCOM SOFTWARE MUST BE UPDATED TO VERSION 4...

Page 2: ...DWARE COMPATIBILITY WITH THE MT 180 MONITOR TESTER RESISTORS R245 AND R219 HAVE BEEN REMOVED TO DISABLE THIS CIRCUIT IF SPECIAL FUNCTION 2 INPUT IS REQUIRED R245 AND R219 75K OHMS 1 4W SHOULD BE INSTA...

Page 3: ...2 15 Memory Test 7 2 16 Watchdog Monitoring Disabled Indicator 8 2 17 Red Failure Monitor Disabled Indicator 8 2 18 Diagnostic Display Mode 210E 2010 8 2 18 1 No Fault Diagnostic Display 8 2 18 2 Fau...

Page 4: ...2 Y VDC FAILED Indicator 24 5 1 3 R WDT ERROR Indicator 24 5 1 4 CONFLICT Indicator 24 5 1 5 RED FAIL Indicator 24 5 1 6 DUAL IND Indicator 24 5 1 7 CLEARANCE Indicator 24 5 1 8 PCA Indicator 25 5 1 9...

Page 5: ...it Connector P1 33 9 1 1 Sixteen Channel 33 9 1 2 Eighteen Channel 34 9 2 Program Card Connector 34 9 2 1 Sixteen Channel 34 9 2 2 Eighteen Channel 35 9 3 Red Interface Connector P8 36 9 4 EIA 232 Con...

Page 6: ...ns January 1989 When triggered by the detection of a fault condition which exists longer than the minimum period the Signal Monitor will enter the fault mode causing the Output relay contacts to close...

Page 7: ...g the Stop Time output to the controller The WDT Latch option see Section 4 5 1 determines whether this WDT Error fault mode is latched through an AC Line brownout or not If the WDT Latch option is no...

Page 8: ...tile EEPROM device is utilized to retain fault status information and event logs in the event of an AC Line power interruption The correct fault indications will be displayed upon restoration of AC Li...

Page 9: ...ed out bulb may be detected as an active signal due to load switch leakage current and may cause a Dual Indication fault Dual Indication Monitoring may also anticipate a possible Conflict in the event...

Page 10: ...e option can be selected see Section 4 5 2 which provides a flash interval of at least 6 seconds and at most 10 seconds in duration following a power up an AC Line interruption or a brownout restore D...

Page 11: ...from 1000 ms minimum to 10 4 seconds maximum Recurrent Pulse detection can be disabled with the RP DISABLE option switch SW3 2 see Section 4 4 2 2 8 EXIT FLASH When the Signal Monitor series exits th...

Page 12: ...DIAGNOSTIC indicator on the front panel will illuminate to indicate a monitor hardware and or firmware failure This type of failure is configured as latching With latching operation only a loss of AC...

Page 13: ...can display the active Green Yellow and Red field status individually To enter this display mode depress and hold the Reset button Each time the Reset button is activated and held the next set of col...

Page 14: ...he model 210E unit has not been triggered by a fault the fault status display mode will show the Green Yellow and Red channels active when the Program Card was removed If a PCA fault is displayed duri...

Page 15: ...he model 210ECL unit has not been triggered by a fault the fault status display mode will show the Green Yellow and Red channels active when the Program Card was removed If a PCA fault is displayed du...

Page 16: ...A channel pair is enabled for FYA operation the Signal Monitor will monitor the FYA logical channel pair for the following fault conditions 2 20 1 1 1 CONFLICT Channel conflicts are detected based on...

Page 17: ...from the solid Green Arrow 13 14 15 16 to the solid Red Arrow 1 2 3 4 without a minimum clearance time on the solid Yellow Arrow 1 2 3 4 when SSM switch 1 2 3 4 is On The fault channel status will be...

Page 18: ...Turn Channels Ga Opposing Through Channels Permissive Turn Channels Ra Ya fYa Green Arrow Signal Driver Source 13 2 1 9 Yellow Ped 14 4 3 10 Yellow Ped 15 6 5 11 Yellow Ped 16 8 7 12 Yellow Ped 2 20...

Page 19: ...ault channel status will also be indicated for the solid Green Arrow channel 9 10 11 12 IF the solid Green Arrow was active The SSM Switch for each 1 3 5 and 7 channel must be in the ON position to en...

Page 20: ...Section 4 4 8 1 2 20 3 FYAC COMPACT MODE H The Model 2010 NYC does support FYA Mode H operation WARNING IF THE PERMISSIVE FLASHING YELLOW ARROW AND PROTECTED GREEN ARROW CHANNEL ASSIGNMENTS ARE SWAPP...

Page 21: ...f operation 3 2 2 EDI ECCOM MONITOR REPORT The EDI ECcom software package Version 3 8 or greater is required interfaces a Computer to the ECL and ECLip models The ECcom program will display the Status...

Page 22: ...Enable Configuration Fault Enable Red Cable Fault enable AC Brownout timing e Watchdog Programming Watchdog Enable Watchdog timing and Watchdog Latch f Configuration Check Value the value of the 16 b...

Page 23: ...Type 01 Firmware V5 0 Comm V3 6 RMS Engine Firmware Type 01 RMS Engine Firmware V2 3 ECcom Version 3 6 2 Downloaded at 10 13 48 AM Friday September 22 2006 Number of events 10 A symbol indicates that...

Page 24: ...lse ENABLED Watchdog Timing 1 5 seconds GY Enable DISABLED FYAC Mode H DISABLED LEDguard Thresholds ENABLED Red Fail Enabled by SSM DISABLED Dual Indication Fault Timing 350 500 ms WDT Error Clear on...

Page 25: ...ction is in hardware flash 4 1 2 SPECIAL FUNCTION PREEMPT INPUTS SF1 SF2 The pins numbered 8 and 6 of Red Interface connector P8 are Special Function SF inputs 1 and 2 respectively NYCDOT These inputs...

Page 26: ...MMING The Signal Monitor provides switch options to modify the monitor operation The Option switches are labeled OPTIONS SW3 and are located near the program card edge connector 4 4 1 RED FAIL TIMING...

Page 27: ...ed through an AC Line brownout or not If the WDT Latch select is not jumpered an AC Line brownout condition will reset the WDT ERROR fault mode when the AC Line is restored The WDT Error indicator wil...

Page 28: ...ates fault or flash mode operation 4 5 7 FYA FLASHRATE MONITOR DISABLE SEL15 The Signal Monitor will respond to an enabled flashing Yellow Arrow signal that is not flashing at a minimum rate see Secti...

Page 29: ...dicator will illuminate when a controller Watchdog fault is detected If the WD ENABLE switch is placed in the OFF position to disable Watchdog monitoring or the AC Line voltage is below the Watchdog d...

Page 30: ...to the DTR signal in the false state while a frame is in the transmit queue 5 1 12 CHANNEL STATUS INDICATORS 210E 2010 During normal operation the 210E 2010 model Channel Status indicators will displ...

Page 31: ...ired inputs for the Signal Monitor to monitor the Red Field Signal outputs It is polarized to insure proper mating with the adapter cable Ejector latches are included to facilitate removal and prevent...

Page 32: ...ed to interconnect the main microprocessor to the following circuit blocks EEprom U21 Real Time Clock U29 24Vdc Logic Processor U41 Display Multiplexer U1 Program Card and Switch inputs U25 4 and the...

Page 33: ...hannel The resulting data is transferred to the main MPU via the SPI interface The analog to digital converter U39 provides the voltage measurement data for the RMS Engine approximately every 6 micros...

Page 34: ...ce fault D No internal watchdog pulses SOLUTIONS A The PCA indicator on the front panel will illuminate Re insert the program card with the diode side of the card facing the front panel slot and depre...

Page 35: ...Eberle Design Inc Page 30 CAUSES Diode on the Program Card is open or absent SOLUTIONS Check the program card to verify that the required diode is in place If the diode is present then verify all conn...

Page 36: ...rms Special Function Inputs no detect less than 50 Vrms detect greater than 70 Vrms Watchdog Enable AC level enable greater than 94 _ 2 Vrms disable less than 91 _ 2 Vrms LEDguard Low Threshold Signal...

Page 37: ...milliseconds typical 1350 milliseconds Dual Indication no fault less than 200 milliseconds fault greater than 500 milliseconds typical 400 milliseconds Dual Indication Long no fault less than 700 mill...

Page 38: ...YELLOW T UNASSIGNED 17 UNASSIGNED U CHANNEL 10 YELLOW 18 CHANNEL 12 YELLOW V CHANNEL 12 GREEN 19 UNASSIGNED W UNASSIGNED 20 CHASSIS GROUND X UNASSIGNED 21 AC Y DC GROUND 22 WATCHDOG TIMER Z EXTERNAL R...

Page 39: ...NNEL 11 YELLOW S CHANNEL 11 GREEN 16 CHANNEL 9 YELLOW T CHANNEL 18 YELLOW 17 CHANNEL 18 GREEN U CHANNEL 10 YELLOW 18 CHANNEL 12 YELLOW V CHANNEL 12 GREEN 19 CHANNEL 17 RED W CHANNEL 18 RED 20 CHASSIS...

Page 40: ...BIT COMMON FF NO CONNECT Mating connector shall be keyed between pins 24 and 25 and also BB and CC The Monitor circuit and the Program Card mate with a 28 56 pin double sided edge card connector havin...

Page 41: ...NNEL 1 RED 10 CHANNEL 11 RED 20 RED ENABLE Note Pin 4 may be used to connect the monitor chassis to the cabinet CHASSIS GROUND To complete this connection a soldered wire jumper must be placed in loca...

Page 42: ...5 DCD pin H should be connected to 5 pin D on the Controller Unit connector CTS pin M should be connected to RTS pin J on the Controller Unit connector 9 5 ETHERNET LAN PORT The Ethernet port must be...

Page 43: ...2010ECL NYC SERIES SIGNAL MONITOR OPERATIONS MANUAL Eberle Design Inc Page 38...

Reviews: