background image

–  1  –

1. Unpack the Switch and Check Contents

AS7512-32X, 
AS7712-32X or 
AS7716-32X

Rack Mounting Kit—2 front-post brackets, 2 rear-post 
brackets, 20 screws, and 2 ear-locking screws

Power Cord (included with AC PSUs only)

Ground Wire (included with DC PSUs only)

Console Cable—RJ-45 to DB-9

DC Power Cable (included with 48 VDC PSU only)

Documentation—

Quick Start Guide

 (this document) 

and 

Safety and Regulatory Information

Note:

 The switch has the Open Network Install 

Environment (ONIE) software installer pre-loaded on the 
switch, but no switch software image. Information about 
compatible switch software can be found at 

www.edge-core.com

.

Caution: 

The switch includes plug-in power supply (PSU) 

and fan tray modules that are installed into its chassis. All 
installed modules must have a matching airflow direction. 
That is, if the installed power modules have a front-to-back 
(F2B) airflow direction, all the installed fan tray modules 
must also have a F2B airflow direction. 

Note:

 The switch drawings in this document are for 

illustration only and may not match your particular switch 
model.

2. Attach the Brackets

Attach each of the front- and rear-post brackets to the 
switch using four of the included bracket screws.

Use an additional two screws to secure each of the rear-post 
brackets at the mid-point on the sides of the switch.

3

1

1

2

1

2

Use the screws and cage nuts supplied with the rack to 
secure the switch in the rack. 

Caution:

 Installing the switch in a rack requires two 

people. One person should position the switch in the rack, 
while the other secures it using the rack screws.

装置の吸排気に必要な領域を マニ ュ アル上に規定 し て
い る 。

3. Adjust Rear-Post Bracket Ears

Lock the position of the rear-post bracket ears using the 
included position-locking screws.
You can also adjust the rear-post bracket ears to fit different 
rack depths from 56 cm to 75 cm.

4. Ground the Switch

Ensure the rack is properly grounded and in compliance 
with ETSI ETS 300 253. Verify that there is a good electrical 
connection to the grounding point on the rack (no paint or 
isolating surface treatment).

Attach the grounding wire #14 AWG to the grounding point 
on the switch rear panel. Then connect the other end of the 
wire to rack ground.
For details on grounding the switch with a 12 VDC PSU in an 
Open Rack, refer to the Edgecore ORSA-1U Open Rack Tray 
Set 

Installation Guide

.

Caution:

 The earth connection must not be removed 

unless all supply connections have been disconnected.

3

1

1

1

2

1

2

150200001281A R04

E052018-AP-R04

www.edge-core.com

32-Port 100G Fiber Ethernet Switch

Q ui c k   St a r t   G u i d e

AS7512-32X | AS7712-32X | AS7716-32X

Summary of Contents for AS7512-32X

Page 1: ...he included bracket screws Use an additional two screws to secure each of the rear post brackets at the mid point on the sides of the switch 3 1 1 2 1 2 Use the screws and cage nuts supplied with the...

Page 2: ...air cable Not required if the NOS installer is located on attached storage Note The RJ 45 Mgmt port of AS7716 32X only supports 1000 Mbps mode Boot the switch Wait for the ONIE software to locate and...

Page 3: ...4 3 A 12 VDC 54 52 9 A 48 VDC PSU Power Rating 48 VDC 650 Watts DC Input 36 72 VDC 16 A maximum DC Output 5 VDC 4 A 12 VDC 52 9 A 12 VDC PSU PSU 12V 750 DC Input 12 VDC from Open Rack busbar Regulato...

Page 4: ...DC PSU RJ 45 DB 9 DC 48 VDC PSU Open Network Installer Environment ONIE www edge core com PSU F2B F2B 2 3 1 1 2 1 2 3 56 cm 75 cm 4 ETSI ETS 300 253 14 AWG 12 VDC PSUs Edgecore ORSA 1U Open Rack Tray...

Page 5: ...c PLA03F7000 AA 36 72 VDC DC 6 LED PSU1 PSU2 Diag LED 2 1 3 1 2 3 4 3 2 1 1 3 2 4 1 1 7 NOS 5 5e RJ 45 Mgmt NOS AS7716 32X RJ 45 Mgmt 1000 Mbps ONIE NOS NOS ONIE NOS ONIE NOS NOS 8 RJ 45 100 ohm 5 5e...

Page 6: ...650 DC 36 72 VDC 16 A DC 5 VDC 4 A 12 VDC 52 9 A 12 VDC PSU PSU 12V 750 DC 12 VDC EN 55032 2012 AC 2013 Class A EN 61000 3 2 2014 Class A EN 61000 3 3 2013 FCC Class A VCCI Class A CCC GB 9254 2008 C...

Page 7: ...x2 x2 x20 x2 AC PSU DC PSU RJ45 DB 9 DC 48 VDC PSU ONIE www edge core com F2B F2B 2 3 1 1 2 1 2 3 56 cm 75 cm 4 ETSI ETS 300 253 14 AWG 12 VDC PSUs Edgecore ORSA 1U Open Rack Tray Set 3 1 1 1 2 1 2 32...

Page 8: ...tronic PLA03F7000 AA 36 72 VDC DC 6 LED PSU1 PSU2 Diag LED 2 1 3 1 2 3 4 3 2 1 1 3 2 4 1 1 7 NOS 5 ohm 5 5e RJ 45 Mgmt NOS AS7716 32X RJ 45 Mgmt 1000 Mbps ONIE NOS NOS ONIE NOS ONIE NOS NOS 8 RJ 45 10...

Page 9: ...DC 650 DC 36 72 VDC 16 A DC 5 VDC 4 A 12 VDC 52 9 A 12 VDC PSU PSU 12V 750 DC 12 VDC EN 55032 2012 AC 2013 Class A EN 61000 3 2 2014 Class A EN 61000 3 3 2013 FCC Class A VCCI Class A CCC GB 9254 2008...

Reviews: