![Edco HCP-2 Operator'S Instruction Manual Download Page 13](http://html1.mh-extra.com/html/edco/hcp-2/hcp-2_operators-instruction-manual_2357325013.webp)
E-PAC5,8,1.5,HCP-2-1008
Printed in USA
TVW
©2008
Page 13
100 Thomas Johnson Drive, Frederick, MD 21702-4600 USA
Phone (301) 663-1600 • 1-800-638-3326
Fax (301) 663-1607 • 1-800-447-3326
Website: www.edcoinc.com
Email: [email protected]
OPERATING INSTRUCTIONS
Prior to initial starting, make sure the crankcase is fi lled to the designated level (within the notched area on the dip-
stick).
DO NOT USE A DETERGENT OIL!
Use a premium grade Air Compressor Oil. Any questions call EDCO at
1-800-638-3326 for information.
DO NOT OVERFILL WITH OIL! OVER FILLING MAY FORCE OIL BETWEEN MOTOR COMPONENTS RESULT-
ING IN COMPLETE MOTOR BURN-UP.
The Compressor should be started and stopped with the ON/OFF switch ONLY. Never unplug the compressor while
the unit is running. Never plug the unit in unless the power switch is in the off position.
START STOP CONTROL
When the pressure in the tank reaches a designated low level, the pressure switch starts the motor. When the pres-
sure in the tank reaches a designated high level, the pressure switch stops the motor. Single stage compressors cut in
at approximately 105 P.S.I.G. and cut out at approximately 135 P.S.I.G.
To increase pressure setting out of storage tank, simply lift up on outside of regulator (yellow adjusting knob) and turn
clockwise until desired pressure is reached. Push outside of knob back down to lock adjustment in place.
ADJUSTING AIR FLOW
USE & MAINTENANCE
Regular maintenance insures trouble free operation. Your new compressor represents the fi nest engineering and
construction available.
Even the fi nest machinery requires periodic maintenance.
On initial start-up, let the com-
pressor run for a few minutes with the drain cock open. The close the drain cock and adjust the in-line regulator as
desired.
!!!!ALWAYS RUN UNIT IN A LEVEL POSITION!!!!
Temperature
0-40º
40º & Above
NON-DETERGENT - Straight Weight
10WT*
30WT*
OIL TYPE TABLE
*For maximum performance and service life, we recommend using a Premium Quality compressor oil.
IMPORTANT, DO NOT MIX STANDARD AND SYNTHETIC OILS
MAINTENANCE
Always unplug or shut down your air compressor and completely drain air tanks before attempting any type
of maintenance!
IMPORTANT:
Replace the oil after the fi rst 50 hours (2 weeks) of operation. Retorque head bolts to 8 ft/lbs after fi rst
200 hours (4 weeks) of operation.
Daily
Every 2 weeks or
100 hours
Monthly or
200 hours
Annually or
2000 hours
1. Drain moisture from tank
2. Check oil level & fi ll as needed.
1. Repeat daily procedures
2. Clean or replace intake fi lter
3. Change oil
4. Check vibration pads
1. Repeat above procedures
2. Check for leaks or any loose parts and correct
3. Check and replace worn or missing rubber feet
1. Repeat monthly procedures
2. Replace the oil in the compressor
3. Check the valves and rings on the compressor and replace if damaged or worn
FAILURE TO COMPLY WITH THE ABOVE RECOMMENDATIONS WILL VOID THE WARRANTY !!