17
REFER TO DAMPER MANUFACTURER'S
INSTALLATION INSTRUCTIONS FOR
POSITION OF DAMPER
CONTROL BOX
ACCEPTABLE VENT
DAMPER LOCATIONS
BOILER
HOT WATER HEATER
CHIMNEY
UN-ACCEPTABLE
DAMPER LOCATIONS
1.
Verify only boiler is serviced by vent damper. See
Figure 10
.
2.
Clearance of not less than 6 inches between vent
damper and combustible material must be maintained.
Additional clearance should be allowed for service of
Vent Damper.
3.
Vent damper must be in open position when appliance
main burners are operating.
4.
Vent damper position indicator must be in visible
location following installation.
5.
Thermostat's heat anticipator must be adjusted to
match total current draw of all controls associated with
boiler during heating cycle.
8 - VENT DAMPER INSTALLATION & INSTRUCTIONS
Figure 9 - Damper Installation
Figure 10
- Damper Location
NOTE:
Refer to
Figure 9
for steps 1-6.
1.
Place Vent Damper on or as close to vent outlet of
boiler as possible. Do not modify draft hood or vent
damper during installation.
2.
Remove Vent Damper Motor cover.
3.
Feed damper wire harness connector through bracket
hole on damper motor frame.
4.
Tighten locknut onto Damper wire harness connector.
5.
Plug Damper connector into socket on damper motor
frame.
6.
Replace damper motor cover and wire damper as.