Table 1 - Minimum Room Volume, Indoor Air Only*
Input Mbh
Standard
Method
Known Air Infiltration Rate Method (Air Changes Per Hour)
0.1
0.2
0.3
0.4
0.5
0.6
45
2250
9450
4725
3150
2363
1890
1575
70
3500
14700
7350
4900
3675
2940
2450
96
4800
20160
10080
6720
5040
4032
3360
120
6000
25200
12600
8400
6300
5040
4200
145
7250
30450
15225
10150
7613
6090
5075
175
8750
36750
18375
12250
9188
7350
6125
195
9750
40950
20475
13650
10238
8190
6825
245
12250
51450
25725
17150
12863
10290
8575
295
14750
61950
30975
20650
15488
12390
10325
* Table values based on boiler only. Add volume for any additional appliances.
4 - VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance
with the section “Air for Combustion and Ventilation,” of
the National Fuel Gas Code, ANSI Z223.1 / NFPA 54, or
applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers,
and kitchen ventilation equipment interfere with proper
operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
•
Engineered Installations
. Must be approved by
authority having jurisdiction.
•
Mechanical Air Supply
. Provide minimum of
0.35 cfm per Mbh for all appliances located within
space. Additional requirements where exhaust fans
installed. Interlock each appliance to mechanical air
supply system to prevent main burner operation when
mechanical air supply system not operating.
•
All Indoor Air
. Calculate minimum volume for all
appliances in space. Use a different method if minimum
volume not available.
A. Standard Method.
Cannot be used if known air
infiltration rate is less than 0.40 air changes per
hour. See Table 1 for space with boiler only. Use
equation for multiple appliances.
Volume ≥ 50 ft
3
x Total Input [Mbh]
B.
Known Air Infiltration Rate.
See Table 1 for
space with boiler only. Use equation for multiple
appliances. Do not use an air infiltration rate
(ACH) greater than 0.60.
Volume ≥
21 ft
3
⁄ACH x Total Input [Mbh]
C. Refer to National Fuel Gas Code
for opening
requirements between connected indoor spaces.
•
All Outdoor Air.
Provide permanent opening(s)
communicating directly or by ducts with outdoors.
A. Two Permanent Opening Method
. Provide
opening commencing within 12 inches of top and
second opening commencing within 12 inches of
bottom of enclosure.
Direct communication with outdoors or
communicating through vertical ducts. Provide
minimum free area of 1 in² per 4 Mbh of total
input rating of all appliances in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in² per 2
Mbh of total input rating of all appliances in
enclosure.
B. One Permanent Opening Method
. Provide
opening commencing within 12 inches of top of
enclosure. Provide minimum clearance of 1 inch on
sides/back and 6 inches on front of boiler (does not
supersede clearance to combustible materials).
C. Refer to National Fuel Gas Code
for additional
requirements for louvers, grilles, screens and air
ducts.
•
Combination Indoor and Outdoor Air.
Refer to
National Fuel Gas Code for application information.