![ECR International R15C Installation, Operation & Maintenance Manual Download Page 44](http://html.mh-extra.com/html/ecr-international/r15c/r15c_installation-operation-and-maintenance-manual_2356109044.webp)
ELECTRICAL SPECIFICATIONS
Power Supply
Volt 1–60
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
Electric Heat
Unit Electrical Ratings
Volt
Min
RLA
LRA
FLA
Hp
FLA
Hp
Htr
#
Volt
W
HA
TCA
THA
MCA MOCP Plug
208/
230V
197
7.4
33
0.6
0.08
1.0
0.25
0
N/A
N/A
N/A
9.0
N/A
10.9
15
HARD
WIRE
3
208
2454
11.8
12.4
15.5
20
230
3000
13
13.6
17.1
4
208
3271
15.7
16.3
20.4
25
230
4000
17.4
18
22.5
5
208
4089
19.7
20.3
25.3
30
230
5000
21.7
22.3
27.9
265V
240
6
28
0.67
0.08
1.3
0.25
0
N/A
N/A
N/A
8.0
N/A
9.5
15
3
265
3983
15
15.7
19.6
20
4
265
5310
20
20.7
25.9
30
5
N/A
N/A
N/A
N/A
N/A
N/A
Table 18 R60 - Cooling Capacity 15,000 BTU Electrical Specifications
Power Supply
Volt 1–60
Compressor
Indoor Fan
Motor
Outdoor Fan
Motor
Electric Heat
Unit Electrical Ratings
Volt
Min
RLA
LRA
FLA
Hp
FLA
Hp
Htr
#
Volt
W
HA
TCA
THA
MCA MOCP Plug
208/
230V
197
8.3
44
0.6
0.08
1.0
0.25
0
N/A
N/A
N/A
9.9
N/A
12
20
HARD
WIRE
3
208
2454
11.8
12.4
15.5
20
230
3000
13
13.6
17.1
4
208
3271
15.7
16.3
20.4
25
230
4000
17.4
18
22.5
5
208
4089
19.7
20.3
25.3
30
230
5000
21.7
22.3
27.9
Table 19 R60 - Cooling Capacity 18,000 BTU Electrical Specifications
The Right Fit for Comfort
44
P/N 240010545, Rev. B [10/24/2014
]