15
D. Vent Termination
о
Venting system shall terminate at least 3 feet
(0.9m) above any forced air inlet located within
10 feet (3m).
о
Venting system shall terminate at least 4 feet
(1.2m) below, 4 feet (1.2m) horizontally from,
or 1 foot (300 mm) above any door, window, or
gravity air inlet into any building.
о
Bottom of vent shall be located at least 12
inches (300mm) above grade.
о
Termination of vent shall be not less than 7 feet
(2.13m) above adjacent public walkway.
о
Vent terminal shall not be installed closer than
3 feet (0.9m) from inside corner of L shaped
structure.
о
Termination of vent should be kept at least 3
feet (0.9m) away from vegetation.
о
United States
- Terminate vent system at least
4 feet (1.22m) horizontally from, and in no
case above or below, unless a 4 feet (1.22m)
horizontal distance is maintained, from electric
meters, gas meters, regulators and relief
equipment. See Figure 9.
HORIZONTAL VENTING INSTRUCTIONS
Figure 9 - Horizontal Venting Clearances
о
Canada -
Terminate vent system at least 6
feet (1.83m) horizontally from, and in no case
above or below,unless 6 feet (1.83m) horizontal
distance is maintained, from gas and electric
meters, regulators and relief equipment.
о
Venting system shall terminate at least 4 feet
below any eave, soffit, or roof overhang.
о
Venting system shall not terminate underneath
any deck, patio, or similar structure.
о
Place vent on wall away from prevailing winter
wind. Locate or guard vent to prevent accidental
contact with people or pets.
о
Terminate vent above normal snow-line. Avoid
locations where snow may drift and block vent.
Ice or snow may cause boiler to shut down if
vent becomes obstructed.
о
Under certain conditions, flue gas will condense,
forming moisture. Take steps to prevent building
materials at vent terminal from being damaged
by exhaust of flue gas.
Summary of Contents for Olsen OSVB II Series
Page 23: ...23 WIRING DIAGRAMS Figure 12 Control Module Damper is not an option...
Page 37: ...NOTES...
Page 38: ...38 NOTES...
Page 39: ...39 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD...
Page 40: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...