30
NO
NO
YES
FIGURE 6-3 - Low Water Cutoff - Detail
6.6 External Optional Low Water Cut Off
These guidelines are supplied when necessary to install an
additional Low Water Cut Off (LWCO), for sensing a low water
level condition in a boiler, as required by the Authority Having
Jurisdiction.
Follow LWCO manufacturer installation instructions for type of
LWCO selected in addition to these instructions.
LWCO shall be 120V/60HZ control and dry contacts sized for
load being connected. Wire control to boiler. See Figure 6-4.
Connect LWCO device to the system ground. Ground in
accordance with the requirements of the authority having
jurisdiction or, in the absence of such requirements, with the
National Electrical Code (NEC) or Canadian Electrical Code
CEC.
•
Locate LWCO sensing device in the supply
piping, above the minimum height of boiler.
See Figure 6-2, Piping Diagram.
•
Position control in HORIZONTAL piping to assure proper
boiler protection (upright or 90° rotation).
•
For proper operation, sensing element of the LWCO
control shall be positioned in the tee to sense the main
water stream. Maintain minimum 1/4” spacing from pipe
walls. Element shall NOT contact the rear, or side walls of
the tee. See Figure 6-3.
•
Install an air vent using a tee to avoid nuisance
shutdowns.
•
Apply small amount of pipe sealant to threaded
connections.
•
Arrange piping to prevent water dripping onto boiler.
•
DO NOT install water shutoff valve between boiler and
LWCO sensing device.
Low Water Cutoff (LWCO)
Electrical Conduit
J-Box
120 V/60 HZ
Conduit or Power
Supply cord
(Polarized)
L
1
N
G
GND
L
1
N
GND
BLK
WHT
120 V/60 HZ Socket
(Polarized) 120 V/60 HZ
Cord Set From Boiler
N.O
FIGURE 6-4 - LWCO Wiring Diagram
6 - HYDRONIC PIPING
240012879 REV A, [01/31/2020]
Summary of Contents for Dunkirk DCBF-125
Page 63: ...61 A 1 MODELS 125 Heat Only APPENDIX A WIRING DIAGRAMS 240012879 REV A 01 31 2020...
Page 64: ...62 APPENDIX A WIRING DIAGRAMS A 2 MODELS 165 Heat Only 240012879 REV A 01 31 2020...
Page 65: ...63 A 2 MODELS 150 Combi APPENDIX A WIRING DIAGRAMS 240012879 REV A 01 31 2020...
Page 66: ...64 A 4 MODELS 205 Combi APPENDIX A WIRING DIAGRAMS 240012879 REV A 01 31 2020...
Page 67: ...65 NOTES 240012879 REV A 01 31 2020...
Page 68: ...66 NOTES 240012879 REV A 01 31 2020...
Page 99: ...29 MODEL 150F Combi 150F FLOOR STANDING COMBI WIRING DIAGRAM PN 240012875 REV A 01 31 2020...
Page 101: ...31 205F FLOOR STANDING COMBI WIRING DIAGRAM MODEL 205F Combi PN 240012875 REV A 01 31 2020...
Page 106: ...36 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240012875 REV A 01 31 2020...
Page 114: ...44 NOTES PN 240012875 REV A 01 31 2020...