The overload alarm light (RED) ① will be always ON
(Red) when an overload of power of all connected electrical devices is detected.
The electrical breaker will activate to stop the power generation in order to
protect the generator and connected electric devices. The AC output indicator
(Green) will be off, and the overload alarm light (red) will stay on, but the
generator will not stop running.
When the overload indicator light is ON, and power generation stops, proceed as
follows:
1. For generator with reset function, disconnect all
electric devices, reduce total wattage of connected
electric devices within the application range, and press
the reset button ①, generator will recover to output.
2.
For generator without reset function, disconnect all
electric devices and stop engine.
3. Reduce total wattage of connected electric devices within the application
range.
4. Check the blockages around cooling air inlet and control unit. If any blockage
is found, remove it.
5. Restart the engine after checking.
NOTE:
Generator output automatically resets when engine is stopped and then
restarted.
Overload indicator light may be ON for seconds at first, when using electric
devices that require a large starting current, such as compressor or
submersible pump, but this is not a malfunction.
OUTPUT INDICATOR (GREEN)
When engine is started and output power, the output
indicator is ON.