MASP 22-GB
rev. 3 APR18
Spark
Extinguishing spark detectors alarm state (3 sec.)
Monitoring spark detectors alarm state (3 sec.)
DET LED on (3sec.)
WATER FLOW LED on (3sec.)
After the alarm, blinking light
until RESET (MEMORY function)
DET LED on (3sec.)
After the alarm, blinking light
until RESET (MEMORY function)
STOP LED on (until reset)
Duct valve closes
(until reset)
After the alarm, blinking light
until RESET (MEMORY function)
Yes
Spark
extinguished?
Solenoid valve opens (3 sec.)
Flowing water through the flow
switch and the nozzle
Alarm sounder sounds (for the entire
duration of water flow)
Alarm sounder sounds (3 sec.)
TEST button down
STOP function
Alarm sounder sounds
(until reset)
Fan stops
RESET button down
STOP LED off
Alarm sounder stops
Duct valve opens
Blinking LEDs off (reset MEMORY)
No
STAND-BY
POWER LED on
DET and
WATER FLOW
LEDs blinking
STAND-BY
POWER LED ON
STAND-BY
POWER LED ON
SYSTEMS TYPE “E1” AND “E”
general functions
• OVERLOAD/SHORT CIRCUIT YELLOW LED
Indicates overload or short circuit. Check electrical connections and
push the white slide switch of the thermal circuit breaker (TCB) to
resume normal operation.
• REVERSE POLARITY RED LED
Indicates reverse polarity. Disconnect and reverse power supply
connections.
• POWER GREEN LED
Indicates the presence of the 24Vdc power voltage. Must always
be on.
• EXTINGUISHING DET 1 RED LED
Steady light indicates that the extinguishing spark detector DET 1 is
in alarm state (standard time 3 sec at each spark detected), blinking
light (until manual RESET) indicates that there was an alarm.
• EXTINGUISHING DET 2 RED LED
Steady light indicates that the extinguishing spark detector DET 2 is
in alarm state (standard time 3 sec at each spark detected), blinking
light (until manual RESET) indicates that there was an alarm.
• WATER FLOW BLUE LED
Operated by the nozzle flow switch, indicates a water flow in the
spray nozzle during an extinguishing operation, or else a water
leakage through a defective solenoid valve. It lights up with a steady
light during extinguishing and in case of water leakage due to valve
defective, blinks until manual RESET to signal that there was an
alarm.
• MONITORING DET 3 RED LED
Steady light indicates that the monitoring spark detector DET 3 is in
alarm state (standard time 3 sec at each spark detected), blinking
light (until manual RESET) indicates that there was an alarm.
• MONITORING DET 4 RED LED
Steady light indicates that the monitoring spark detector DET 4 is in
alarm state (standard time 3 sec at each spark detected), blinking
light (until manual RESET) indicates that there was an alarm.
• STOP RED LED
Indicates an alarm for un-extinguished spark and stop circuit
activated. This LED lights together with MONITORING DET LED but
it turns off only when the RESET button is pressed.
• TEST BUTTON
Used to check the system.
A short pulse causes a spark to be simulated inside the detectors,
that will go in alarm state: they will activate the alarm sounder, will
cause the EXTINGUISHING DET, MONITORING DET and STOP
LEDs to light on and will stop the fun.
The WATER FLOW LED is controlled by the flow switch and will
therefore light only if water flows through the nozzle. This LED
doesn’t turn on only in case of malfunction (jammed nozzles,
solenoid valve closed).
If during the test do not turn on one or more DET LEDs, the related
detectors are not connected or are faulty.
• RESET BUTTON
Resets the memory, switches off the STOP LED, turns off the sound
alarm and opens the stop circuit.
The system returns to normal operating conditions.
Warning!!!
Fast impulsive electromagnetic noise in the factory can cause false alarms. To avoid them we suggest to take a few measures during wiring of spark detectors such as
good ground connection of metallic parts and of shields of shielded cables and to keep separate 24Vdc wiring from higher voltage wiring (A. C. power line).
If possible, run wiring through metallic tubing. Keep spark detectors wiring physically separate from other wiring (motor controls and other high power loads).
For further information see note on false alarms on pages MASP26 and following.