MASP 10-GB
rev. 3 MAR17
MOUNTING OF SPARK DETECTOR
RIV-601P/S
WITH
SAM-871
MOUNTING FRAME
Double detector (pair)
Single detector
CONTR
OL
LOGIC
DET
DET
duct
•
•
•
SPARK DETECTORS installed on duct
Spark detector is not installed directly over the duct but through the SAM-871
mounting frame which
isolates it
from the duct itself.
Spark detector is put inside the SAM-871 mounting frame and it sees the duct
internal through two optical windows. Whatever situation will happen inside the
duct does not go externally.
In order to assure the isolation, we strongly recommend the installer to follow the
mounting instructions on pages MASP 9-10 of the application manual.
Obviously the installer must take care that mounting operations and related
accessories will guarantee the perfect isolation.
Mounting holes on ducting
(dimensions in mm)
55
110
Ø 62
60
30
30
55
No. 6 holes with appropriate size for
the type of mounting (rivets,
self-threading screws or other)
taking into consideration that the
holes on the frame have a diameter
of 6mm