Press and hold the pushbutton 
switch while applying 24VAC power 
to the actuator. The red LED blinks 
once, pauses and blinks twice, 
pauses and blinks three times, etc.  
Release the switch after the 
number of blinks corresponding to 
the Address to be set.

The Address number can be reset 
at any time.

Turn power Off to the actuator.  

2.

1.

 Changing the Damper Home Address

The dampers are factory set for Address 1 and only need to be 
changed when two or more installations are within 300’ of one 
another.

Push button

switch

Red LED

Press and hold the pushbutton 
switch and the green LED blinks 
once, pauses and blinks twice, 
pauses and blinks three times, etc.  
Release the switch after the 
number of blinks corresponding to 
the Zone number to be set.

The zone number can be reset at 
any time.

1.

 Changing the Damper Zone Number

The dampers are factory set for Zone1 and Address 1 and only 
need to be changed when more than one thermostat is used in 
an installation.

Push button

switch

Green LED

Setting Bypass

The R80DWL Damper actuator has a Close position limit that 
can be used to insure minimum airflow even when the damper 
has been set to 0% Airflow. The minimum Close Position can 
be set from about 50% closed to fully closed.

Close Cam

Close Cam

Set Screw

Set Screw

Cam Cover

Cam Cover

Set the damper to the fully open position by applying 24VAC to 
24VAC terminals. 

Loosen the set screw and rotate the Close Cam clockwise and 

gently

 tighten the set screw. With the cam set in the fully 

counter clockwise position, the damper will completely close. 
In the fully clockwise position, the damper will close to about 
50% closed allowing some air to pass even when the user sets 
the damper to fully closed. Replace the cam cover.

Limited 5-Year Warranty

The 5-year warranty is limited to the repair or replacement of 
defective product due to parts failure or defective workmanship.

26072 Merit Circle #110 / Laguna Hills, CA 92653

949-916-0945 Fax 949-458-8502 

www.eControlsUSA.com

eControls

eControls

Use the steps below to test the installation to insure the 
dampers are wired and set properly.

 3) Testing Communication

Turn power On to the actuator and observe the dampers go 
to the fully open position and the Green LED turns On.  

Press the 

System

 key to display Heat. Press the 

Down 

key until the setpoint temperature is several degrees lower 
than the Inside Temperature. The damper goes to the 
closed position and the Red LED is On.

Press the 

Up

 key until the setpoint temperature is several 

degrees higher than the Inside Temperature. The damper 
goes to the fully open position indicated by the Green LED 
on or a modulated position indicated by the Green and Red 
LEDs blinking.

1.

2.

3.

Solid green LED indicates open damper position.

i

Solid red LED indicates closed damper position.

i

i

Green and red LEDs blinking indicates damper is in a 
modulated position.

Power Failure - When power is restored, the damper will 
go to a fully open position and resume communication 
with the Remote Control. 
The Remote Control will automatically refresh the 
position of the dampers every 15 minutes to the last set 
airflow provided the Remote Control is powered and 
within 125’ of the damper.

i

 2)  Damper Wiring (Continued)

Summary of Contents for T200WLD

Page 1: ...low to the space The thermostat maintains the temperature using the system mode and setpoint temperature set by the user and the space temperature Automatically controls airflow based on selected syst...

Page 2: ...Off Heat or Cool The System Mode selected by the user needs to correspond to the current system mode of the HVAC equipment OFF MODE In Off Mode the thermostat sets the airflow to the Off Airflow Leve...

Page 3: ...d NEXT Schedule PM MENU MODE NEXT ENTER SYSTEM Night All days are displayed The number in the upper right corner shows the day of the week being selected or deselected 1 is Monday 2 is Tuesday etc Pre...

Page 4: ...ange is reduced Batteries should be replaced with AA alkaline or lithium batteries Inside Mo Schedule AM Set To MENU MODE NEXT ENTER SYSTEM HEAT Day Inside Mo Schedule AM Set To MENU MODE NEXT ENTER S...

Page 5: ...Range Range Range Range 1 to 8 1 to 8 1 to 5 F o 60 to 90 F o 55 to 80 F o 0 to 100 0 to 100 0 8 F 1 16 F 5 to 30 minutes 0 On with key Default 1 1 1 F o 80 F o 65 F o 50 50 0 8 F 10 minutes On with k...

Page 6: ...thermostat makes an adjustment to the airflow If the deadband is set for 1 degree the room temperature must be more than 1 degree warmer or cooler than the setpoint temperature before the damper posit...

Page 7: ...ss 1 The dampers are powered by 24VAC and require only 2 8VA when operating and only 1VA when holding A 40VA transformer can power up to 10 dampers The damper or dampers controlling airflow to the spa...

Page 8: ...ise position the damper will completely close In the fully clockwise position the damper will close to about 50 closed allowing some air to pass even when the user sets the damper to fully closed Repl...

Reviews: