background image

The Damper position is 
adjusted proportional to the 
differential between setpoint 
and room temperatures. The 
Damper Factor is the percent 
change in damper position or 
airflow for one degree of 
temperature differential.

08  Set Damper Factor

Option

CANCEL

NEXT

ENTER

SYSTEM

Press the 

 keys to set the Damper Factor from 8% 

to 16%.

Press the 

NEXT

 key to go to the next option. Or, press the

 

ENTER

 key to save and exit installer options, or press the

 

CANCEL 

key to exit installer options without saving.

UP/DOWN

The Nighttime Airflow is the 
airflow level that is 
automatically set when using 
the scheduled nighttime 
setback. The lower airflow 
reduces energy consumption.

09  Set Nighttime Airflow

Option

CANCEL

NEXT

ENTER

SYSTEM

Press the 

 keys to set the Nighttime Airflow from 0% 

to 100%.

Press the 

NEXT

 key to go to the next option. Or, press the

 

ENTER

 key to save and exit installer options, or press the

 

CANCEL 

key to exit installer options without saving.

UP/DOWN

The Off Airflow is the airflow 
level that is automatically set 
when the System is set to Off. 
The lower airflow reduces 
energy consumption.

Press the 

UP/DOWN

 keys to

10  Set Off Airflow Level

Option

CANCEL

NEXT

ENTER

SYSTEM

set the Off Airflow from 0% to 100%.

Press the 

NEXT

 key to go to the next option. Or, press the

 

ENTER

 key to save and exit installer options, or press the

 

CANCEL 

key to exit installer options without saving.

 1)  Damper Installation

 2)  Damper Wiring

To 24VAC

Transformer

24VAC

24VAC

Wireless Airflow Control

Model A80WLD

Modulating
24VAC, 2.8VA

eControls

Laguna Hills, CA
Made in USA

Z#

A#

The dampers are factory set for Zone1 and Address 1.

The dampers are powered by 
24VAC and require only 2.8VA 
when operating and only 1VA 
when holding.

A 40VA transformer can power 
up to 10 dampers.

The damper or dampers controlling airflow to the space should 
be installed in the supply duct providing airflow to the space.  
In commercial installations the damper can be installed into the 
supply diffuser.

The dampers should be mechanically supported and sealed 
after installation. Although the dampers can be installed in any 
orientation, it is desirable to install them where the LED 
indicators on the damper actuators can be seen to verify they 
are opening and closing.

Skip this option. The LCD 
uses LEDs to light the display. 
Battery operated thermostats 
light the LCD only when a key 
is pressed to maintain battery 
life. This option is set to 00 
and cannot be changed.

05  LCD Backlight

Option

CANCEL

NEXT

ENTER

SYSTEM

Press the 

 key to go to the next option. Or, press the

ENTER

 key to save and exit installer options, or press the

 

CANCEL 

key to exit installer options without saving.

NEXT

 

The High Setpoint Limit is the 
highest setpoint temperature 
the user can set.

Press the 

 keys to 

set the High Setpoint Limit 
from 60 to 90 degrees.

UP/DOWN

06  Set High Setpoint Limit 

Option

CANCEL

NEXT

ENTER

SYSTEM

Press the 

 key to go to the next option. Or, press the

ENTER

 key to save and exit installer options, or press the

 

CANCEL 

key to exit installer options without saving.

NEXT

 

The Low Setpoint Limit is the 
lowest setpoint temperature 
the user can set.

Press the 

 keys to 

set the Low Setpoint Limit 
from 55 to 80 degrees.

UP/DOWN

07  Set Low Setpoint Limit

Option

CANCEL

NEXT

ENTER

SYSTEM

Press the 

 key to go to the next option. Or, press the

ENTER

 key to save and exit installer options, or press the

 

CANCEL 

key to exit installer options without saving.

NEXT

 

7

Summary of Contents for T200WLD

Page 1: ...low to the space The thermostat maintains the temperature using the system mode and setpoint temperature set by the user and the space temperature Automatically controls airflow based on selected syst...

Page 2: ...Off Heat or Cool The System Mode selected by the user needs to correspond to the current system mode of the HVAC equipment OFF MODE In Off Mode the thermostat sets the airflow to the Off Airflow Leve...

Page 3: ...d NEXT Schedule PM MENU MODE NEXT ENTER SYSTEM Night All days are displayed The number in the upper right corner shows the day of the week being selected or deselected 1 is Monday 2 is Tuesday etc Pre...

Page 4: ...ange is reduced Batteries should be replaced with AA alkaline or lithium batteries Inside Mo Schedule AM Set To MENU MODE NEXT ENTER SYSTEM HEAT Day Inside Mo Schedule AM Set To MENU MODE NEXT ENTER S...

Page 5: ...Range Range Range Range 1 to 8 1 to 8 1 to 5 F o 60 to 90 F o 55 to 80 F o 0 to 100 0 to 100 0 8 F 1 16 F 5 to 30 minutes 0 On with key Default 1 1 1 F o 80 F o 65 F o 50 50 0 8 F 10 minutes On with k...

Page 6: ...thermostat makes an adjustment to the airflow If the deadband is set for 1 degree the room temperature must be more than 1 degree warmer or cooler than the setpoint temperature before the damper posit...

Page 7: ...ss 1 The dampers are powered by 24VAC and require only 2 8VA when operating and only 1VA when holding A 40VA transformer can power up to 10 dampers The damper or dampers controlling airflow to the spa...

Page 8: ...ise position the damper will completely close In the fully clockwise position the damper will close to about 50 closed allowing some air to pass even when the user sets the damper to fully closed Repl...

Reviews: