background image

6

Touch the 

 keys to 

change the minimum off time 
(minutes) before restarting the 
compressor. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation.

UP/DOWN

NEXT

 ENTER

Option

NEXT

ENTER

Option

NEXT

ENTER

Touch the 

 keys to 

change the minimum run time 
(minutes) before turning a 
system off. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation.

UP/DOWN

NEXT

 ENTER

Option

NEXT

ENTER

Touch the 

 keys to 

change the minimum off time 
(minutes) before restarting a 
gas furnace or electric strip 
heater. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation.

UP/DOWN

NEXT

 ENTER

Touch the 

 keys to 

select 0, 1, 2. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation, or touch 
the hidden 

 key to return 

to the previous option.

UP/DOWN

NEXT

 ENTER

BACK

Option

NEXT

ENTER

0

1

2

o

Turns cooling On 1 above setpoint and Off at Setpoint.

 

o

o

Turns cooling On 1  above setpoint, Off .5 below Setpoint.

 

Turns cooling On 1  above setpoint, Off 1  below Setpoint.

o

o

Turns heating On 1  below setpoint and Off at Setpoint.

o

o

o

Turns heating On 1  below setpoint, Off .5 above Setpoint.

 

o

o

Turns heating On 1 below setpoint, Off 1  above Setpoint

 

.

Touch the 

 key to select ON 

to turn on smart recovery or 
touch the 

 key to select 

OF to turn smart recovery off. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation.

UP

DOWN

NEXT

 ENTER

Smart recovery initiates a heating or cooling call so that the space is 
at temperature when the setback period ends.

Option

NEXT

ENTER

Touch the 

 keys to 

select the heating temperature 
when the space is vacant. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation, or touch 
the hidden 

 key to return 

to the previous option.

UP/DOWN

NEXT

 ENTER

BACK

Option

NEXT

ENTER

Touch the 

 keys to 

select the cooling temperature 
when the space is vacant. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation, or touch 
the hidden 

 key to return 

to the previous option.

UP/DOWN

NEXT

 ENTER

BACK

Option

NEXT

ENTER

Cool

Vacant

Vacant

Touch the 

 keys to 

change the downstairs (Inside) 
temperature to the temperature 
that the user feels is correct. 

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation, or touch 
the hidden 

 key to return 

to the previous option.

UP/DOWN

NEXT

 ENTER

BACK

Inside

Option

NEXT

ENTER

Heat

Touch the 

UP/DOWN

 keys to 

change the upstairs (Inside2) 
temperature to the temperature 
that the user feels is correct. 

Touch 

NEXT

 to display the 

next option, or

 ENTER

 to save 

the option and return to normal 
thermostat operation, or touch 
the hidden 

BACK

 key to return 

to the previous option.

Inside2

Option

NEXT

ENTER

Touch the 

 keys to 

set the time in minutes to 
update the upstairs and 
downstairs airflow.  

Touch 

 to display the 

next option, or

 to save 

the option and return to normal 
thermostat operation, or touch 
the hidden 

 key to return 

to the previous option.

UP/DOWN

NEXT

 ENTER

BACK

Option

NEXT

ENTER

This is the frequency, in minutes, that the damper position is updated.

04  Compressor Minimum Off Time

Factory Default: 2 Minutes. Range: 0 to 9 Minutes

05  Heating Minimum Off Time

Factory Default: 0 Minutes. Range: 0 to 9 Minutes

06  Minimum Run Time

Factory Default: 2 Minutes. Range: 0 to 9 Minutes

10  Vacant Cooling Setpoint

o

o

Range: 74 F to 95 F

o

Factory Default: 80 F.

09  Vacant Heating Setpoint

o

o

Range: 44 F to 75 F

o

Factory Default: 65 F.

07  Setting On-Off Temp Differential

Factory Default: #1. Range: 0, 1 or 2.

08  Smart Recovery

Factory Default: Off. Range: On or Off.

11  Calibrate Downstairs Temperature Sensor

Factory Default: None.

o

Range - +/-5

12  Calibrate Upstairs Temperature Sensor

Factory Default: None.

o

Range - +/-5

13  Airflow Update Time

Factory Default: 2 Minutes. Range: 1 to 20 Minutes.

Summary of Contents for Comfort 365 C365T11

Page 1: ...ing only Cooling only Automatic Heating or Cooling Maximum upstairs and downstairs heating and cooling airflow limits are set during installation Option used when bedrooms are located upstairs C365 uses the upstairs temperature sensor to control heating and cooling calls and directs more airflow upstairs One Model TS5 10 or two Model TS5 20 upstairs temperature sensors can be used Round or rectang...

Page 2: ...the battery cover downward and install the two AA batteries as shown R C W EQUIPMENT Y G Upstairs Sensor COM COM CLS CLS OPN OPN Upstairs Downstairs Install an R80CT damper in the duct supplying air to the upstairs and wire the terminals to the corresponding terminals on the C365T Install a second R80CT damper in the duct supplying air to the downstairs and wire it to the C365T Each damper uses 2 ...

Page 3: ... upstairs and downstairs dampers There are separate terminals for the upstairs and the downstairs dampers Multiple dampers can be used to construct the upstairs or downstairs zones Daisy chain terminals COM to COM OPN to OPN and CLS to CLS Use 2 conductor 18 or 20 gage thermostat cable to wire from the C365 Thermostat to the upstairs temperature sensor C365 Terminal C365 Terminal C365 Terminal R C...

Page 4: ... and Day NEXT ENTER AM Touch the UP DOWN keys to change the HOUR Touch NEXT to save the hour and go to change the minute CHANGE THE HOUR Touch the UP DOWN keys to change the MINUTE Touch NEXT to save the minute and go to change the day of the week CHANGE THE MINUTE Touch the UP DOWN keys to change the DAY OF THE WEEK Touch ENTER to save the day fo the week and return to thermostat operation CHANGE...

Page 5: ... L 5 0 Airflow Update Time A F t 1 to 20 minutes 2 ACCESSING INSTALLER OPTIONS To access the Installer Options and the hidden Enter key for 7 seconds until the first Option appears on the screen TOUCH HOLD Inside Tu Day Upstairs Auto Downstairs Airflow COOL Schedule AUTO FAN MENU MODE Cool Set To SYSTEM AM TOUCH HOLD and this key for 7 seconds to access the Installer Options Touch the keys to set ...

Page 6: ...e previous option UP DOWN NEXT ENTER BACK Option NEXT ENTER Touch the keys to select the cooling temperature when the space is vacant Touch to display the next option or to save the option and return to normal thermostat operation or touch the hidden key to return to the previous option UP DOWN NEXT ENTER BACK Option NEXT ENTER Cool Vacant Vacant Touch the keys to change the downstairs Inside temp...

Page 7: ...ion NEXT ENTER Cool Touch the keys to select the maximum allowable downstairs airflow in heating Touch to display the next option or to save the option and return to normal thermostat operation or touch the hidden key to return to the previous option UP DOWN NEXT ENTER BACK Downstairs Airflow Option NEXT ENTER Heat Touch the keys to select the maximum allowable downstairs airflow in cooling Touch ...

Page 8: ...stairs Airflow in Heating Upstairs Downstairs Airflow NEXT ENTER Heat To determine the maximum allowable downstairs airflow touch the key until the airflow is too great and causes noise or annoyance Increase the airflow using the key until it is acceptable This is the maximum allowable downstairs airflow in heating Record the airflow value DOWN UP Maximum Allowable Downstairs Airflow in Heating 05...

Reviews: