Page 14
ecom-DP3
5.2. Natural gas
5.2.1. Stress test
The stress test acc. to DVGW – TRGI Process
Instructions G 600 at gas pipes (operation pressure
up to 100 hPa) is registered as a control pragram in
the
ecom-DP3
. Proceed as follows:
1. Scroll with the cursor keys
<up/down>
in the
menu
"Natural gas"
to the menu point
„Stress
test“
. Activate the menu point with
<Enter>
.
2. Check if necessary the values of stabilisation time,
measurement time and test pressure with
<F1>
(back with
<ESC>
).
3. Lock the gas pipe with a suitable adapter (test
stopple, high pressure stopple or one-pipe counter
cap).
4. Connect the components as described in
chapter 3.
5. Start the control program with
<Enter>
(the pump
of the instrument is building up the adjusted pres-
sure).
6. Wait for stabilisation time (if the pressure remains
in the range „test pressure - 10%" during stabilisation
time, so the measurement time will start). If neces-
sary the stabilisation time can be terminated with
<F1>
.
7. Once the measurement time is over, the result is
displayed and can be printed with
<Print>
.
8. If the menu
„Stress test“
is selected again, so
the result can be called up with
<F4>
(as long as the
ecom-DP3
is switched on) or a new measurement
can be started with
<F1>
.
Stress test
1Bar/1000hPa TRGI 2018
Stabilisation time
Res. time: 58sec
Pressu 1003.1hPa -0.8hPa
Temp. 22.6°C 0.3°C
Start Difference
1002.3
hPa
Stress test
1Bar/1000hPa TRGI 2018
Measur. in process
Res. time: 9:25min
Pressu 1002.3hPa 0.0hPa
Temp. 22.6°C 0.0°C
Start Difference
1002.3
hPa
Stress test
1Bar/1000hPa TRGI 2018
Set value 1000hPa
is built up!
902.3
hPa
1min
10min
Stress test
1Bar/1000hPa TRGI 2018
Connect!
Forward w.:
Set value 1000
hPa
0.0
hPa
Stress test
1Bar/1000hPa TRGI 2018
Measurement 10:00min
Ini. Press 1002.3hPa
Fin. Press 1002.3hPa
Difference 0.0hPa
Ini. temp. 22.6°C
End temp. 22.6°C
Difference
0.0°C
Forward w.:
Stress test
1Bar/1000hPa TRGI 2018
Start new
measurement?
Select:
YES
NO
Summary of Contents for DP3