OPERATION OF BURNER WITH LIGHT-OIL FUEL  MULTICALOR 300.1-400.1

Once installed the burner,  check the following items:
- The burner power feeding and the main line protection fuses
- The correct length of pipes and that the same are sealed.
- The type of fuel, which must be suitable for burner.
- The connection of boiler’s thermostats and all the safeties.
- The motor rotation direction.
- The correct calibration of the motor’s thermal protection.
When all the above mentioned conditions are checked and accomplished, it is possible to go on with burner’s tests. Power the
burner. The control box feeds the ignition transformer and the burner’s motor at the same time, which will run a prepurging of
the combustion chamber. At the end of prepurging,  the control box powers up the ignition transformer and opens the light-oil
valve, so the burner start . the servomotor will set up to the light-oil ignition position, whilst the control box powers up the
ignition transformer and the “Safety” and “Low flame” solenoid valves. After a safety interval of 2 seconds and a correct igni-
tion, the control box turns off the ignition transformer and, 10 seconds later, sets the motorised air damper to its maximum
opening and opens the 2nd stage solenoid valve (Multicalor 300.1) and 3rd stage solenoid valve (Multicalor 400.1). In case of
faulty ignition,the control box will shut down the burner in 2 sec.
In order to obtain a correct combustion, it shall be necessary to adjust the Low and High flame by following the instructions of
the Air servomotor and firing head adjustment.
During such a phase, it will be possible to manually switch between HIGH and LOW flame and viceversa, through the
High/Low flame switch. At the end of the adjusting phase, leave the switch in position “AUTO”. The fuel pump feeding pres-
sure, must remain around 12 bar. 

0

1

2

0 - STOP
1 - GASOLIO
2 - GAS

Multicalor 300.1

Multicalor 400.1

LIGHT-OIL

Summary of Contents for Multicalor 300.1

Page 1: ...techniques for energy saving G A S T E C GAS LIGHT OIL DUAL BURNERS LB1203 24 10 2003 Multicalor 300 1 Multicalor 400 1 Light oil Natural gas 40 300 mbar MODEL...

Page 2: ...230 400 230 400 Motor kW 5 5 7 5 Motor s RPM N 2800 2800 Fuels Nat Gas LHV 35 9 Mj Nm3 8 570 kcal Nm3 Light Oil LHV 10 200 kcal kg max 1 5 at 20 C mbar 1500 2000 2500 3000 3500 4000 10 12 14 16 1000...

Page 3: ...tats close the leakage control device runs a valves leakage test then enables the burner to start the ignition cycle OPERATION OF BURNER WITH GAS MULTICALOR 300 1 400 1 Before starting the burner make...

Page 4: ...E PRESSURE REGULATOR The pressure regulator complete with its incorporated filter must be installed to avoid contaminants reaching the gas valve It is important to ensure certain conditions The pressu...

Page 5: ...justment gas output take out the cap L and loose the nut F Adjust the screw E with a screwdriver To reduce output turn counter clockwise to increa se it turn clockwise Tighten the nut F B The pressure...

Page 6: ...causes a drop in test pressure the device puts the system into the safety condition and the red pilot right on the device lights up The flame control device starts the burner fan to carry out prewash...

Page 7: ...r situated on the control panel on position 1 and proceed as follows Adjusting the maximum gas flow rate see figure on solenoid valve adjustments or adjust the gas pressure in the governor ADJUSTING T...

Page 8: ...pag 8 techniques for energy saving LB1203 MULTICALOR 300 1 400 1 REMOVING THE BLAST TUBE REMOVING THE FIRING HEAD FIRING HEAD SETTING...

Page 9: ...s up the ignition transformer and opens the light oil valve so the burner start the servomotor will set up to the light oil ignition position whilst the control box powers up the ignition transformer...

Page 10: ...UMP 1 2 5 6 3 4 1 INLET 2 RETURN 3 BLEED AND PRESSURE GAUGE PORT 4 VACUUM GAUGE PORT 5 PRESSURE ADJUSTMENT 6 TO NOZZLE SUNTEC TA3C40105 6 5 3 2 SUNTEC 1 4 SUNTEC J7CCC10014P NOZZLE PUMP PRESSURE bar G...

Page 11: ...the position of electrodes after having replaced the nozzle see illustration A wrong position could cause ignition troubles A pulsante di sblocco B operating lamps orange light oil green gas C Selecto...

Page 12: ...wn out The control box is faulty THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE Check the fan and the air pressure Check the air pressure switch Control box faulty Ignition...

Page 13: ...00 1 400 1 Multicalor 300 1 400 1 7 8 36 11 38 14 4 6 5 3 9 10 41 26 31 29 30 27 34 32 33 35 28 42 43 37 21 13 12 25 24 22 23 19 20 17 16 15 18 25 24 1 46 45 44 40 2 39 47 49 56 57 53 54 48 52 51 50 5...

Page 14: ...OIL SELECTOR R1020 5 R1020 5 21 SELECTOR R1020 5 22 LAMP Elettrospring EL N SC4 E1510 E1510 23 FUSE SUPPORT FUSIT FH B528 E802 2 E802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R906 25 REL F...

Page 15: ...PUMP MOTOR 740 W M147 M147 51 OIL VALVE Parker SCEM VE 140 V175 1 V175 1 52 COIL Parker SCEM VE 140 53 OIL VALVE DELTA 1 8 F F F84 V420 V420 54 COIL DELTA 1 8 F F F84 55 OIL FILTER 1 X1 7010 1 S103 1...

Page 16: ...GAS LIGHT OIL SELECTOR R1020 5 R1020 5 21 SELECTOR R1020 5 22 LAMP Elettrospring EL N SC4 E1510 E1510 23 FUSE SUPPORT FUSIT FH B528 E802 2 E802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R90...

Page 17: ...E Parker SCEM VE 140 V175 1 V175 1 52 COIL Parker SCEM VE 140 53 OIL VALVE DELTA 1 8 F F F84 V420 V420 54 COIL DELTA 1 8 F F F84 55 OIL FILTER 1 X1 7010 1 S103 1 X1 03 S107 5 56 GAS VALVE BRAHMA E6GSR...

Page 18: ...P 95 96 SAMA 1 2 3 0 FMV 95 96 SPA SPGmin HLG HLg YVg1 YVg2 YVgS pos 1 ALTA FIAMMA HIGH FLAME 2meALLURE ALTA LLAMA pos 3 AUTOMATICO AUTOMATIC AUTOMATIQUE AUTOMATICO INTERRRUPTEUR 2me 1re ALLURE pos 2...

Page 19: ...DE 1 LLAMA FIRST STAGE OIL SOLENOID VALVE ELECTROVANNE MAZOUT PETITE ALLURE ELECTROVALVULA DE GASOLEO 1 LLAMA YVg2 YVg1 YVG1 TELERRUPTOR MOTOR VENTILATOR CONMUTADOR GASOLEO GAS INTERRUPTEUR MAZOUT GAS...

Page 20: ...FIRMA DATA FIRMA CONTROLLATO DESCRIZIONE MODIFICA DISEGNATO DATA FIRMA COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE A TERMINE DI LEGGE E VIETATO RIPRODURRE O CONTROLLO DI TENUTA APPARECCHIATURA UFF TE...

Page 21: ...DE 1 LLAMA ELETTROVALVOLA GAS DI PRIMA FIAMMA ELECTROVALVULA DE GASOLEO 2 LLAMA YVg2 YVg1 YVG1 REMOTE CONTROL SWITCH FAN MOTOR THERMOSTAT CHAUDIERE CONMUTADOR MANUAL AUTOMATICO INTERRUPTEUR MANUEL AU...

Page 22: ...pag 22 techniques for energy saving LB1203 MULTICALOR 300 1 400 1...

Page 23: ...pag 23 techniques for energy saving LB1203 MULTICALOR 300 1 400 1...

Page 24: ...principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ecoflam it e mail ecoflam ecoflam it ECOFLAM S p A reserve...

Reviews: