MULTICALOR 300.1÷400.1

ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH

Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of  gas nominal feed
pressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for
L.P.G. nom. pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw
up cover M

ADJUSTMENT OF THE AIR PRESSURE SWITCH

Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by
turning regulator D to position 1. 
- Start the burner and keep in low flame running, while checking that combustion is cor-
rect. Through a small cardboard, progressively obstruct the air intake until to obtain a
CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressure
port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase the
adjustment value of the air pressure switch until to have the burner lockout. Remove the
obstruction from the air intake, screw on the cover C and start the burner by pressing the
control box rearm button.

Note: The pressure measured at pressure port E must be within the limits of the pressure
switch working range. If not, loose the locking nut of screw F and gradually turn the same: clockwise
to reduce the pressure; counterclockwise to increase. At the end tighten the locking nut.

2,5

5

10

15

50

2

5

35

30

40

45

20

0,4

0,6

0,9

3,0

1,5

2,1

1,8

2,4

2,7

1,2

I

L

M

N

A

B

C

D

E

F

G

H

gas pressure 

switch

air pressure switch

LEAKAGE CONTROL DEVICE DUNGS VPS 504-VDK 200 

When the thermostats are closed, the gas leakage control device checks the valve seals by pressurizing the circuit between the
two gas valves. When test pressure is reached the device remains in stand-by for about 25 seconds. At the end of the test the yel-
low pilot light on the control device lights up and the burner is enabled to carry out the start-up cycle. If the seal on one of the
valves is faulty and this causes a drop in test pressure, the device puts the system into the safety condition and the red pilot right
on the device lights up. The flame control device starts the burner fan to carry out prewashing of the
combustion chamber,checking fan air pressure via the air pressure switch. After preventilation the igni-
tion transformer starts operating, generating a spark between the electrodes and simultaneously the gas
valves open (safety gas valve VS and first stage operating valve VL). If the flame does not ignite or goes
out, total safety is ensured by an ionization detection probe. The safety time limit in the event of no
flame is less than 2 seconds at start-up and less than 1 during operation. In the event of no gas being
supplied or of a considerable drop in pressure the minimum gas pressure switch interrupts burner operation. About 20/30
seconds after ignition the flame control device commands operation of the second stage via the gas valve and air servocontrol,
thus taking the burner to maximum power.

VL 

VS 

DISPOSITIVO
CONTROLLO

TENUTA

LANDIS & STAEFA SQM 50.381A2 AIR DAMPER MOTOR

Remove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key provided

for. Description: 

I

- High flame operating opening position adjusting cam (Light-Oil /Gas)

II

- Ignition flame opening position adjusting cam (Gas).

III

- Low flame operating opening position adjusting cam (Gas)

IV

- Low flame operating opening position adjusting cam ( Light-Oil)

V

- 2nd flame solenoid valve opening On/Off cam (Light-Oil)

VI

- Not used cam

VII

- Not used cam

VIII

- Not used cam

Multicalor 300.1

Cam VIII 
is never used

LEAKAGE

CONTROL

DEVICE

I -

High flame operating opening position adjusting air cam

II -

Ignition flame opening position adjusting air cam (Gas/Light-Oil)

III -

Low flame operating opening position adjusting cam (Gas)

IV -

Low flame operating opening position adjusting cam (Light-Oil)
(always 3° lesser than Low flame adjusting V cam)

V -

Low flame operating opening position adjusting air cam (Light-Oil)

VI -

Low flame solenoid valve opening On/Off cam (Light-Oil)

VII

-

High flame solenoid valve opening On/Off cam (Light-Oil)

VIII

- Not used cam

Multicalor 400.1

Summary of Contents for Multicalor 300.1

Page 1: ...techniques for energy saving G A S T E C GAS LIGHT OIL DUAL BURNERS LB1203 24 10 2003 Multicalor 300 1 Multicalor 400 1 Light oil Natural gas 40 300 mbar MODEL...

Page 2: ...230 400 230 400 Motor kW 5 5 7 5 Motor s RPM N 2800 2800 Fuels Nat Gas LHV 35 9 Mj Nm3 8 570 kcal Nm3 Light Oil LHV 10 200 kcal kg max 1 5 at 20 C mbar 1500 2000 2500 3000 3500 4000 10 12 14 16 1000...

Page 3: ...tats close the leakage control device runs a valves leakage test then enables the burner to start the ignition cycle OPERATION OF BURNER WITH GAS MULTICALOR 300 1 400 1 Before starting the burner make...

Page 4: ...E PRESSURE REGULATOR The pressure regulator complete with its incorporated filter must be installed to avoid contaminants reaching the gas valve It is important to ensure certain conditions The pressu...

Page 5: ...justment gas output take out the cap L and loose the nut F Adjust the screw E with a screwdriver To reduce output turn counter clockwise to increa se it turn clockwise Tighten the nut F B The pressure...

Page 6: ...causes a drop in test pressure the device puts the system into the safety condition and the red pilot right on the device lights up The flame control device starts the burner fan to carry out prewash...

Page 7: ...r situated on the control panel on position 1 and proceed as follows Adjusting the maximum gas flow rate see figure on solenoid valve adjustments or adjust the gas pressure in the governor ADJUSTING T...

Page 8: ...pag 8 techniques for energy saving LB1203 MULTICALOR 300 1 400 1 REMOVING THE BLAST TUBE REMOVING THE FIRING HEAD FIRING HEAD SETTING...

Page 9: ...s up the ignition transformer and opens the light oil valve so the burner start the servomotor will set up to the light oil ignition position whilst the control box powers up the ignition transformer...

Page 10: ...UMP 1 2 5 6 3 4 1 INLET 2 RETURN 3 BLEED AND PRESSURE GAUGE PORT 4 VACUUM GAUGE PORT 5 PRESSURE ADJUSTMENT 6 TO NOZZLE SUNTEC TA3C40105 6 5 3 2 SUNTEC 1 4 SUNTEC J7CCC10014P NOZZLE PUMP PRESSURE bar G...

Page 11: ...the position of electrodes after having replaced the nozzle see illustration A wrong position could cause ignition troubles A pulsante di sblocco B operating lamps orange light oil green gas C Selecto...

Page 12: ...wn out The control box is faulty THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE Check the fan and the air pressure Check the air pressure switch Control box faulty Ignition...

Page 13: ...00 1 400 1 Multicalor 300 1 400 1 7 8 36 11 38 14 4 6 5 3 9 10 41 26 31 29 30 27 34 32 33 35 28 42 43 37 21 13 12 25 24 22 23 19 20 17 16 15 18 25 24 1 46 45 44 40 2 39 47 49 56 57 53 54 48 52 51 50 5...

Page 14: ...OIL SELECTOR R1020 5 R1020 5 21 SELECTOR R1020 5 22 LAMP Elettrospring EL N SC4 E1510 E1510 23 FUSE SUPPORT FUSIT FH B528 E802 2 E802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R906 25 REL F...

Page 15: ...PUMP MOTOR 740 W M147 M147 51 OIL VALVE Parker SCEM VE 140 V175 1 V175 1 52 COIL Parker SCEM VE 140 53 OIL VALVE DELTA 1 8 F F F84 V420 V420 54 COIL DELTA 1 8 F F F84 55 OIL FILTER 1 X1 7010 1 S103 1...

Page 16: ...GAS LIGHT OIL SELECTOR R1020 5 R1020 5 21 SELECTOR R1020 5 22 LAMP Elettrospring EL N SC4 E1510 E1510 23 FUSE SUPPORT FUSIT FH B528 E802 2 E802 2 24 REL BASE Finder 5532 R905 R905 Finder 5534 R906 R90...

Page 17: ...E Parker SCEM VE 140 V175 1 V175 1 52 COIL Parker SCEM VE 140 53 OIL VALVE DELTA 1 8 F F F84 V420 V420 54 COIL DELTA 1 8 F F F84 55 OIL FILTER 1 X1 7010 1 S103 1 X1 03 S107 5 56 GAS VALVE BRAHMA E6GSR...

Page 18: ...P 95 96 SAMA 1 2 3 0 FMV 95 96 SPA SPGmin HLG HLg YVg1 YVg2 YVgS pos 1 ALTA FIAMMA HIGH FLAME 2meALLURE ALTA LLAMA pos 3 AUTOMATICO AUTOMATIC AUTOMATIQUE AUTOMATICO INTERRRUPTEUR 2me 1re ALLURE pos 2...

Page 19: ...DE 1 LLAMA FIRST STAGE OIL SOLENOID VALVE ELECTROVANNE MAZOUT PETITE ALLURE ELECTROVALVULA DE GASOLEO 1 LLAMA YVg2 YVg1 YVG1 TELERRUPTOR MOTOR VENTILATOR CONMUTADOR GASOLEO GAS INTERRUPTEUR MAZOUT GAS...

Page 20: ...FIRMA DATA FIRMA CONTROLLATO DESCRIZIONE MODIFICA DISEGNATO DATA FIRMA COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE A TERMINE DI LEGGE E VIETATO RIPRODURRE O CONTROLLO DI TENUTA APPARECCHIATURA UFF TE...

Page 21: ...DE 1 LLAMA ELETTROVALVOLA GAS DI PRIMA FIAMMA ELECTROVALVULA DE GASOLEO 2 LLAMA YVg2 YVg1 YVG1 REMOTE CONTROL SWITCH FAN MOTOR THERMOSTAT CHAUDIERE CONMUTADOR MANUAL AUTOMATICO INTERRUPTEUR MANUEL AU...

Page 22: ...pag 22 techniques for energy saving LB1203 MULTICALOR 300 1 400 1...

Page 23: ...pag 23 techniques for energy saving LB1203 MULTICALOR 300 1 400 1...

Page 24: ...principali Ecoflam S p A via Roma 64 31023 RESANA TV Italy tel 0423 715345 r a telefax 0423 715444 Italy 480009 Export 480873 715538 http www ecoflam it e mail ecoflam ecoflam it ECOFLAM S p A reserve...

Reviews: