Ecoflam ECOMAX 3SC 1000-N Installation, Use And Maintenance Manual Download Page 14

14

Technical features and dimensions

(*) Minimum dimensions for boiler room access.
(**) Pressure drops corresponding to a thermal variation of 15K.

ECOMAX 3SC 3900-N÷6100-N

fig. 17 

T1 Heating flow
T2 Heating return
T3 Expansion vessel connection
T4 Boiler drain

T5 Chimney connection
T6 Burner connection
T7 Inspection door
T8 Condensation drain

1  Panel board
2  Burner connection flange
3  Smoke chamber cleaning door
4  Flame sight glass

ECOMAX 3SC 

Model

ECOMAX 3SC 

Model

DIMENSIONS

A

mm

2088
2088
2214
2214
2380
2380

B

mm
226
226
240
240
240
240

2533
2533
2653
2653
2860
2860

C*

mm

417
417
437
437
509
509

D

mm

485
485
515
515
595
595

E

mm

F

mm

1437
1437
1550
1550
1650
1650

G

mm
987
987

1007
1007
1100
1100

H

mm
170
170
167
167
224
224

I

mm

4738
4738
4928
4928
5484
5484

L

mm
323
323
323
323
325
325

1475
1475
1475
1475
2920
2920

M

mm

1665
1665
1815
1815

670
670

N

mm

363
363
363
363
465
465

O

mm

1700
1700
1700
1700
1850
1850

Q*

mm

R*

mm

Useful 

output

kW

2925÷3900
3300÷4400
3600÷4800
3900÷5200
4275÷5700
4575÷6100

Furnace

output

kW

3042.1÷4094.4
3432.1÷4619.3
3744.1÷5039.3
4056.1÷5459.2
4446.1÷5984.1
4758.1÷6404.1

Boiler

capacity

l

6012
6012
7058
7058
7909
7909

Water side

pressure

drop(

**

)

m.w.c.

0.28÷0.50
0.35÷0.63
0.42÷0.75
0.50÷0.88
0.59÷1.05
0.68÷1.21

Flue gas

pressure

 drop

mm.w.c.

44.4÷78.6

56.6÷100.5

50.5÷92.2

59.3÷105.4

49.5÷90.5

56.7÷100.7

Maximum

operating

pressure

boiler

bar

6
6
6
6
6
6

Weight

kg

8630
8630
9675
9675

13060
13060

CONNECTIONS

T1

T2

UNI 2278 PN16

T3

UNI 2278 PN16

DN 125
DN 125
DN 125
DN 125
DN 125
DN 125

DN 250
DN 250
DN 250
DN 250
DN 250
DN 250

T4

ISO 7/1

Rp 1½
Rp 1½
Rp 1½
Rp 1½
Rp 1½
Rp 1½

T5

Øi

mm

660
660
660
660
720
720

T6

Ø

mm

500
500
500
500
500
500

T7

Ø

mm

133
133
133
133
133
133

3826
3826
3976
3976
4380
4380

fig. 18 

Cemento refrattario

Piastra porta-bruciatore cieca 700x700

Guarnizione piastra porta-bruciatore 700x700

ø

 5

00

ø

 5

00

240

DETAIL FOR DOOR DRILLING

3900-N÷5200-N

3900-N
4400-N
4800-N
5200-N
5700-N
6100-N

DETAIL FOR DOOR DRILLING

5700-N÷6100-N

Cemento refrattario

Piastra porta-bruciatore cieca 700x700

Guarnizione piastra porta-bruciatore 700x700

ø

 5

00

ø

 5

00

282

fig. 19 

3900-N
4400-N
4800-N
5200-N
5700-N
6100-N

T8

Øe

mm

40
40
40
40
40
40

B

A

Q

R

O

N

M

L

I

D

E

G

G

C

F

T4

T8

H

T2

T5

T6

T1-T3-T2

T3

T1

T6

T7

4

2

3

1

Blind burner plate 700x700

Burner plate insulation gasket 700x700

Refractory cement

Blind burner plate 700x700

Burner plate insulation gasket 700x700

Refractory cement

Summary of Contents for ECOMAX 3SC 1000-N

Page 1: ...INSTALLATION USE AND MAINTENANCE to be keep by the consumer www ecoflam burners com Technical data ECOMAX 3SC 80 N 6100 N Operating instructions Electric diagrams Spare parts list 05 04 2018 EN...

Page 2: ...Important note 22 3 8 Connecting flue exhaust pipe 23 3 9 Condensation drainage 23 3 9 Connecting boiler to system 24 3 9 1 Recirculation pump 24 3 10 Filling the system 24 3 11 Gas connection 25 3 1...

Page 3: ...lusive use of the professionally qualified installer and or maintenance technician in compliance with current legislation The user is NOT qualified to intervene on the boiler The manufacturer will not...

Page 4: ...parts which affect the operating safety of the appliance Attention To tighten or loosen the screwed fittings use only appropriate fixed spanners Incompliant use and or inappropriate tools can cause d...

Page 5: ...ctromagnetic compatibility directive 89 336 EEC The essential requirements of the efficiency directive 92 42 EEC 1 6 TECHNICAL DATA PLATE The technical data plate is adhesive and is included in the do...

Page 6: ...repair it or intervene on it directly Contact only personnel qualified in compliance with law Any repairs must be performed solely by personnel authorised by Ecoflam using original spare parts only F...

Page 7: ...m sheet The top part of the shell is provided with hooks for lifting the boiler Note ECOMAX 3SC boilers are intended to operate with ON OFF type GAS burners as an alternative they can be equipped with...

Page 8: ...vided for each boiler on pages 9 14 by the burner technician who will determine the fuel flow rate In all cases turbulators must be positioned inside their respective smoke pipes resting on the intern...

Page 9: ...1210 1390 1442 1692 C mm 190 190 190 190 190 D mm 305 350 350 421 421 E mm F mm 480 500 500 580 580 G mm 115 130 130 165 165 H mm 1487 1737 I mm 147 157 157 258 258 In the ECOMAX 3SC 200 N and ECOMAX...

Page 10: ...32 2 20 2 35 8 23 7 42 1 Flue gas pressure drop mm w c Maximum operating pressure boiler bar 6 6 6 6 Weight kg 665 845 986 1119 ECOMAX 3SC Model DIMENSIONS A mm 860 890 890 890 B mm 1210 1275 1470 17...

Page 11: ...1020 Q mm 1504 1699 1894 R mm Furnace output kW 510 680 585 780 652 5 870 CONNECTIONS T1 T2 UNI 2278 PN16 T3 UNI 2278 PN16 T4 UNI 228 T5 i mm T6 mm DN 125 DN 125 DN 125 DN 65 DN 65 DN 65 G 1 G 1 G 1 3...

Page 12: ...2099 7 1833 2467 1 Boiler capacity l 1040 1242 1418 1617 2086 2324 Water side pressure drop m w c 0 11 0 19 0 15 0 26 0 15 0 26 0 20 0 36 0 16 0 28 0 21 0 38 1 Panel board 2 Burner connection flange...

Page 13: ...6 2834 6 2418 1 3254 5 2730 1 3674 5 Boiler capacity l 2667 4142 4455 Water side pressure drop m w c 0 28 0 50 0 37 0 66 0 37 0 65 1 Panel board 2 Burner connection flange 3 Smoke chamber cleaning doo...

Page 14: ...4 1 Boiler capacity l 6012 6012 7058 7058 7909 7909 Water side pressure drop m w c 0 28 0 50 0 35 0 63 0 42 0 75 0 50 0 88 0 59 1 05 0 68 1 21 Flue gas pressure drop mm w c 44 4 78 6 56 6 100 5 50 5 9...

Page 15: ...loss at casing min max Heat loss at chimney with burner on min max Heat loss at chimney with burner off min max Flue gas temperature tf ta min max CO 2 content Flue gas mass flow rate min max Nominal...

Page 16: ...96 1 95 2 96 3 95 4 96 3 95 5 0 2 0 2 3 7 4 5 0 1 0 1 75 4 93 4 9 8 9 8 5159 6943 4800 N 3600 4800 3744 1 5039 3 96 1 95 2 96 3 95 4 96 3 95 5 0 2 0 2 3 7 4 5 0 1 0 1 75 4 93 4 9 8 9 8 5628 7575 5200...

Page 17: ...Check that boiler is set up to operate with the available type of fuel This can be seen written on the package and on the technical feature plate c Checkthatthechimney fluehasanappropriate draught wi...

Page 18: ...h LAW March 5 1990 N 46 and relative applicative regulation by Italian Presidential Decree 447 of December 6 1991 and subsequent amendments Safety standards for systems FIELD OF APPLICATION without th...

Page 19: ...dled easily lifting it by means of upper hook s or shifting it on rollers underneath the sturdy base longerons 1000 X XX XX 600 600 3 5 BURNER The burners operating with the ECOMAX 3SC boilers must ha...

Page 20: ...light it could break ATTENTION the flame control warning light can be very hot therefore pay the utmost attention fig 22 3 5 2 INSTALLING THE BURNER Before assembling the burner it is necessary to che...

Page 21: ...after the adjustment Adjustment in the axial direction by adjusting the locking screws 3 7 2 300 N 560 N BOILERS For all these models the door is hinged and fixed according to the layout in fig 23 In...

Page 22: ...d and fixed according to the layout in fig 25 In these cases the two hinges on the left are normally used as rotation hinges from right to left while the two on the right are used as closing hinges It...

Page 23: ...condensation drainage in the sewer must be implemented as to prevent releasing gaseous combustion products into the environment or sewer siphoning dimensioned and implemented to allow the correct out...

Page 24: ...animals and objects for which the manufacturer cannot be held responsible Connection of expansion vessel ECOMAX 3SC boilers are suitable for operating with forced water circulation both with the expa...

Page 25: ...he boiler Attention Make sure that there are no mechanical tension points while connecting gas to avoid the risk of leakage If you smell gas a Do not turn electric switches on or off use a telephone o...

Page 26: ...pliance contains Hydraulic test certificate Heating system booklet System manager operating instructions Installation and maintenance instruction booklet Warranty Local ventilation requirements label...

Page 27: ...bend inside the L shaped profile at the base of the boiler body and hook the upper part in the plate cuts To determine which is the right side and which is the left side refer to the cable glands the...

Page 28: ...nel board frontwards after having removed the two screws on the side and insert the electric inlet cables and the outlet probe capillaries through the slots at the base Fix the panel board to the uppe...

Page 29: ...ctions 1 3 2 4 5 6 5 ECOMAX 3SC 340 N 560 N fig 29 11 4 11 1 8 2 10 12 13 3 14 15 fig 30 1 Thermometer probe 2 Working thermostat probe 3 Safety thermostat probe 4 Minimum thermostat probe 5 Safety sp...

Page 30: ...lectric inlet cables and the outlet probe capillaries through the slots at the base Fix the panel board to the upper panel pos 12 Fit the upper panel pos 12 complete with panel board to the two sides...

Page 31: ...es and the outlet probe capillaries through the slots at the base Fix the panel board to the upper panel pos 9 Fit the upper panel pos 9 complete with panel board to the two sides of the casing E Inse...

Page 32: ...base Fix the panel board to the upper panel pos 8 Fit the upper panel pos 8 complete with panel board to the two sides of the casing E Insert into the conduits the bulbs of the instruments as indicate...

Page 33: ...already mounted C Position the right side panels pos 6 and 3 with the lower bend inside the L shaped profile at the base of the boiler body and hook the upper part in the screws fastened on the top l...

Page 34: ...on the top of the boiler Ref fig 35 of the thermometer pos 1 of the working thermostat pos 2 of the safety thermostat pos 3 of the minimum thermostat pos 4 It is recommended to insert the probes all t...

Page 35: ...e panel board frontwards after having removed the two screws on the side and insert the electric inlet cables and the outlet probe capillaries through the slots at the base fig 36 ECOMAX 3SC 3900 N 61...

Page 36: ...using electric energy requires the observance of some fundamental rules such as do not touch the appliance with wet and or moist parts of the body and or in bare feet do not pull the electric cables...

Page 37: ...is provided with a DPDT contact for the control of a two stage burner The differential between the switching points of the two double pole is 6 C not adjustable The minimum thermostat accessible throu...

Page 38: ...FU FUSE HLB BLOCK BULB SECOND FLAME BULB HL2 RECIRCULATION SWITCH SAC SAL LINE SWITCH STR RECIRCULATION THERMOSTAT STS SECURITY THERMOSTAT STAB HIGH LOW FLAME THERMOSTAT BURNER SWITCH STL WORKING THER...

Page 39: ...P T T P T P T P HL2 STAB STS STR STL HLB SAC SAB HLF FU 6 3 A max SAL C BOILER S CIRCULATOR Q MAIN SWITCH OPERATION BULB HLF FU FUSE HLB BLOCK BULB SECOND FLAME BULB HL2 RECIRCULATION SWITCH SAC SAL...

Page 40: ...N L 2 1 3 17 16 15 4 19 20 21 P T T P T P T P HL2 STAB STS STR STL HLB SAC SAB HLF FU 6 3 A max SAL 60 L10 N N N 83 85 84 61 82 297 296 178 86 73 51C L3 L2 L1 ACCESSORY WIRING ACCESSORY WIRING C BOIL...

Page 41: ...CABLES BURNER BOILER P PAB PR MD SINGLE PHASE OPTIONAL WARNING THE 4 POLES TERMINAL BOARD W4 IS CONNECTED ONLY IF THE BOILER IS COUPLED WITH A PAB PR MD BURNER ACCESSORY WIRING ACCESSORY WIRING BURNE...

Page 42: ...1 20 19 15 16 17 5 T6 T7 T8 B5 L1 N T1 S3 T2 B4 14 13 11 12 8 9 6 7 10 18 J1 4 3 1 2 L N W3 N L1 PE TRIPHASE WIRING CONNECTION ACCESSORY ACCESSORY WIRING ACCESSORY WIRING ACCESSORY WIRING ACCESSORY WI...

Page 43: ...the air vents and the flue gas exhaust system highlighting their essential features and the absolute prohibition of modifying them Inform the system manager concerning control of the system s water pr...

Page 44: ...rs have been designed to be used at the declared nominal output ECOMAX 3SC boilers are equipped with flue gas turbulators inside each smoke duct see page 8 The correct position of the turbulators insi...

Page 45: ...ge 49 Inspection and maintenance instructions To assure long term functioning of your appliance and to avoid altering its approved status only original Ecoflam spare parts must be used Before proceedi...

Page 46: ...deterioration if so it must be replaced using only original spare parts Check the condition of the smoke chamber inspection cover gasket Replace it if worn using only original spare parts Maintenance...

Page 47: ......

Page 48: ...a il diritto di apportare ai prodotti le modifiche che riterr necessarie o utili senza pregiudicarne le caratteristiche principali La maison Ecoflam Bruciatori S p A se r serve le droit d apporter les...

Reviews: