9/61
ESI Outdoor Unit Installation Instruction
05.2018
Manufacturer reserves the right to change at any time for specifications or designs without notice and incurring obligations.
8 Feet Maximum
Side View
8 Feet Maximum
Wall
Isolator
Pipe Set
Secure suction pipe using isolators every 8 ft. Secure liquid pipe directly to
suction pipe using tape, wire, or other appropriate method every 8 ft.
Figure 5-2 Isolation in wall spaces
Sealant
Suction pipe
Insulation
Wall
Figure 5-3 Isolation through wall
Ductwork
Isolator
Pipe Set
Figure 5-4 DO NOT hang pipe sets from ductwork
5. Refrigerant Pipe Routing
Comply with National, State, and Local Codes when isolating pipe sets from joists, rafters, walls, or
other structural elements.
Take precautions to prevent noise within the building structure due to
vibration transmission from the refrigerant pipes. For Example:
•
Use isolation type hangers when the refrigerant pipes have to be fastened to floor joists or other framing.
•
Isolation hangers should also be used when refrigerant pipes traverse stud spaces or enclosed ceilings.
•
Where the refrigerant pipes pass through a wall or sill, it should be insulated and isolated.
•
Isolate the pipes from all ductwork.
•
Minimize the number of 90
º
turns.
Figure 5-1 Isolation from Joist/Rafter
8 Feet Maximum
Side View
8 Feet Maximum
Joist/Rafter
Isolator
Pipe Set
Secure suction pipe from joists using isolators every 8 ft. Secure liquid pipe directly to suction
pipe using tape, wire, or other appropriate method every 8 ft.