34/61
ESI Outdoor Unit Installation Instruction
05.2018
Manufacturer reserves the right to change at any time for specifications or designs without notice and incurring obligations.
Discharge temperature protection
YES
or
1.Error definition:
P3: The maximum detected discharge temperature(TD) is no less than 248F.
E3: System locks up when P3 has occurred six times within 3 hours.
2.Possible causes:
Too little refrigerant remains in the system.
Dirty plugging of TXV(indoor unit).
Damaged discharge temperature sensor.
Damaged main control board.
NO
NO
Reset the sensor or
reconnect the wire
YES
Replace the faulty sensor
YES
Check the refrigerant
amounts
NO
Replace the compressor
Display
Are the stop valves of outdoor unit open?
NO
Open the stop valve
Check whether the discharge temperature sensor is properly seated on
the discharge pipe and securely connected to CN7 terminal on the
main control board.
Check whether the
Resistance of Temperature sensor B*
is correct.
Unplug TD sensor from CN7 and cycle the power. Can it operate under
backup running?
YES
Is there abnormal sound or vibration for compressor?
YES
Replace the main control board
NO