ESI Outdoor Unit Installation Instruction
05.2018
Manufacturer reserves the right to change at any time for specifications or designs without notice and incurring obligations.
13.2 Auto charge mode
Off
Blinking
On
1 minute
1second
SEG1
SEG2
SEG3
Turn on the power supply, choose cooling mode on thermostat . Make sure the setting temperature is
lower than room temperature for at least 5
゜
F.
Press and hold BS4 button for five seconds
, then SEG1 displays blinking “7”. After a minute, the
system will go into AUTO charge mode to lock the compressor frequency.
Note:
Start-up control is enforced to complete prior to activate the AUTO charge mode.
Normally, the 7 segments LED displays refrigerant coefficient on the condition that the system has run
20 minutes for stabilization.
If the LED displays “--” for more than 20 minutes, stop charging and
check the TXV adjustment to ensure proper superheat at the suction pipe.
Maintain a minimum of 5 minutes’ operation after every refrigerant charge or TXV opening adjustment.
[Refrigerant coefficient]
0
0.4
0.6
1.0
Insufficient
Excess
Just
The refrigerant coefficient is used to evaluate the amount of refrigerant.
[Use either way below to end AUTO charge mode]
1. Press
BS4 once
in operation
2. After 2 hours running (Automatically EXIT).
This AUTO charge mode is suitable for ambient temperature between 20~120
º
F. But for the best
results, indoor temperature should be kept between 70~80
º
F.
For outdoor ambient temperature is below 20
゜
F, use weigh-in charge method instead. It is always suggested
to check the charge amount and indoor TXV opening when outdoor ambient temperature is above 20
゜
F.
120ºF
20ºF
80ºF
70ºF
Figure 13-1 LED display in AUTO charge assistant
Figure 13-2 Temperature limit for AUTO charge assistant
a) Outdoor ambient
b) Indoor ambient