Eco Air ECO906SQ Installation Manual Download Page 7

 4

Accessories

 INSTALLATION INSTRUCTIONS

Note:

 The above parts are provided,certain other parts  needed during

             installation  are not provided.

Fig.3

Ensure that the space around the left and 
right of the indoor unit is at least 12cm with
a minimum clearance of 15cm from the 
ceiling.
Use a stud finder to locate studs to prevent 
unnecessary damage to the wall. 
A  minimum pipe run of 3 metres is required 
to minimise vibration & excessive noise.
The indoor unit should be installed on the 
wall at a height of at least 2 metres from
the floor .
Two of the A, B and C directions should be 
free from obstructions.

CAUTION

.

Self-tapping screw  B
ST2.9x10-C-H

Remote  controller
holder

7

8

12cm above

Air Filte

r

12cm

 abo

ve

15cm above

1

2

3

Remote Controller

6

2

 m

  

ab

ov

e

 ( C)

TEMP

AUTO 
COOL
DRY
HEAT

FAN
HIGH
MED
LOW

MODE

FAN SPEED

TIMER ON

SLEEP

ON/OFF

TIMER OFF

        AIR 
 DIRECTION

RESET LOCK

SET TEMPERATURE

        SWING

        LED
    DISPLAY

        TURBO

1

2

3

4

5

6

7

8

Self-tapping Screw B - ST2.9X10 

Remote controller

Installation Plate

Name of Accessories

Self-tapping Screw  A - ST3.9X25

Seal(see page 8 for details)

Drain Plug(see page 8 for details)

Clip Anchor

Number

Q

ty

Remote controller holder

1

8

8

1

1

1

2

1

C

B

A

60cm

 abo

ve

6

0

cm

 ab

ove

30cm

 abov

e

200

cm

 ab

ove

Air Outlet

30c

m a

bov

e

Stop Valve Cover

Summary of Contents for ECO906SQ

Page 1: ...Before using your air conditioner please read this manual carefully and keep it for future reference R410A SPLIT SERIES DC INVERTER QUICK COUPLING Models ECO906SQ ECO1206SQ ECO1806SQ...

Page 2: ...ust be connected to the terminal which is marked with the letter N or coloured BLACK The BROWN wire is the LIVE and must be connected to the terminal which is marked with the letter L or coloured RED...

Page 3: ...ke back the old appliance for disposal when you replace with a new product C Old products contain valuable resources which should be recycled as scrap metal Wild disposal of waste in forests and lands...

Page 4: ...nsure that they do not play with the air conditioner If the power cord is to be replaced replacement work shall be performed by authorised personnel only Installation work must be performed in accorda...

Page 5: ...se electrical shock or fire 6 Use the specified cables for electrical connections between indoor and outdoor units Firmly clamp the cables so that no external stress is placed on the terminal Incorrec...

Page 6: ...e free from the possibility of flammable gas leakage in a nearby place Avoid places near a bedroom and the like so that the noise will not be an annoyance Ensure any local authority permission is soug...

Page 7: ...loor Two of the A B and C directions should be free from obstructions CAUTION Self tapping screw B ST2 9x10 C H Remote controller holder 7 8 12cm above Air Filter 12cm above 15cm above 1 2 3 Remote Co...

Page 8: ...nd corresponding mounting points on the installation plate Dimensions are in mm unless otherwise stated 1 Determine hole positions according to the diagram detailed in Fig 5 Drill one 1 hole 90mm slan...

Page 9: ...on 3 Drainage Installation 1 Run the drain hose sloping downward to ensure condensation water is being drained externally any rise in the drain hose will prevent condensation water to flow externally...

Page 10: ...erly by putting the unit lengthwise along the wall or using a dust or shield plates In coastal or windy area install the unit to prevent the exposure to strong winds If mounting on wall brackets the i...

Page 11: ...that the handle on the male coup ling is in a reclined positio n away from the mating male coupling Step 2 Retract the Release Sleeve on female coupling insert the male coupling located on the indoor...

Page 12: ...ion Step 4 Retract the Release Sleeve on the female coupling to release the male coupling half from the female half Step 5 To seal and protect from dust reinstall the protective cap and plug Electrica...

Page 13: ...or details 4 The test operation may last about 30 minutes Model Power supply Input Rated Amp Switch Fuse 16000Btu h NOTE The supply voltage can not be less than the rate voltage of the air conditioner...

Page 14: ...MEMO Date of installation Purchased from Dealer Name Date of purchase Model number Serial number...

Page 15: ...ing from a faulty installation is specifically excluded This unit must be operated under conditions as recommended at voltages indicated on the unit Any attempts made to service or modify the unit by...

Reviews: