background image

14

Eclipse ExtensoHeat Lance Burners, V1, Installation Guide 235, 5/23/2011

Troubleshooting

Problem

Possible Cause

Solution

Cannot initiate startup
sequence

Air pressure switch has not made contact

Check  air  pressure  switch  adjustment.
Check air filter. Check blower rotation from
blower

High gas pressure switch has tripped

Check incoming gas pressure. Adjust gas
pressure if necessary. Check pressure
switch setting and operation

Low gas pressure switch has tripped

Check incoming gas pressure. Adjust gas
pressure if necessary. Check pressure
switch setting and operation

Insufficient process temperature

Check  the  temperature.  Increase  the
temperature if necessary. Check safety
thermostat settings and operation

Main power is off

Make  sure  the  power  is  on  to  the  control
system

No power to control unit

Call qualified electrician to investigate

Startup sequence runs but
burner does not light

Too much gas: Manual gas balancing
valves have been opened too far

Check pressures and settings against
start-up report and adjust as necessary

Too much gas: Gas pressure out of the
main gas pressure regulator is too high

Check start-up setting. If necessary,
remove regulator and investigate

Not enough gas: Gas pressure out of the
main gas pressure regulator is too low

Check start-up setting. Check regulator
and adjust if necessary

Not enough gas: Start gas solenoid valve
does not open

Check solenoid valve coil for proper
orientation. Replace if necessary

Not enough gas: Gas valve not open

Check wiring to the automatic gas shut-off
valve

Not enough gas; pilot solenoid valve does
not open

Have a qualified electrician check power
supply to solenoid

Not enough pilot gas: Air in the gas line

Check  output  from  the  flame  safeguard.
Open gas cock. Purge gas line

Oxygen and/or temperature levels too low Stop  the  installation and  verify  the  design

data

The low fire flame is weak
and unstable

Low fire adjusted too low

Increase low fire gas setting

Not enough gas

Check start-up settings and adjust to
increase low gas flow

Not enough air

Check  start-up  settings.  Investigate  any
changes, i.e. blocked filter, loose
connections

The burner goes off when it
cycles to high fire

Insufficient air (flame too rich)

Check start-up settings. Check that the air
filter is clean and replace if required

Insufficient oxygen level

Stop  the  burner(s)  and  restore  the
minimum conditions before putting it back
in service

Oxygen and/or temperature levels too low Stop  the  installation and  verify  the  design

data

The burner is erratic and
does not respond to
adjustment

Internal damage to the burner. Some parts
inside the burner may be loose or dirty

Contact Eclipse

Summary of Contents for ExtensoHeat EH050

Page 1: ...Eclipse ExtensoHeat Lance Burners Model EH050 Installation Guide 235 Version 1 5 23 2011...

Page 2: ...nd Eclipse will not be liable for any other injury loss damage or expenses whether direct or consequential including but not limited to loss of use income or damage to material arising in connection w...

Page 3: ...rovals of Components 6 Checklist Before Installation 7 General Installation Conditions 7 Burner Installation 7 Piping 9 Valve Installation 9 Checklist After Installation 9 Adjustment Start and Stop 10...

Page 4: ...4 Eclipse ExtensoHeat Lance Burners V1 Installation Guide 235 5 23 2011 Table of Contents Yearly Checklist 13 Troubleshooting 14 Appendix i Conversion Factors i Key to System Schematics ii...

Page 5: ...ons Control options include on off or group modulation and pulse firing Constant air flow Self ignition by process temperature Flame detection is not necessary Temperature above 1382 F or 750 C Operab...

Page 6: ...o not deviate from any instructions or application limits described herein without written advice from Eclipse Read this entire manual before you attempt to start the system If you do not understand a...

Page 7: ...dent testing agency Typical application examples include American NFPA 86 with listing marks from UL FM CSA European EN 746 2 with CE mark from TuV Gastec Advantica Electrical Wiring All electrical wi...

Page 8: ...ions Mechanical Connect the burner feedings with the corresponding manifold using steel piping or copper in special cases Weld in accordance with both the country s regulation where the equipment will...

Page 9: ...oHeat burners to be installed in case of low temperature level Figure 3 3 ExtensoHeat Burners Distribution The front plate includes a flame viewport with manual latch There is a fixation option with a...

Page 10: ...ion This is an important position indicator If you do not do this somebody may think that the gas cock is in the closed position when it is actually in the open position Gas Balancing Valves A gas bal...

Page 11: ...k that the chamber temperature is above 1382 F 750 C Check that the kiln sweep and burner permissive activation are correct Reset the group control cabinet general safeties if necessary General safety...

Page 12: ...ner Figure 4 2 Fuel Gas Adjustment 7 Use the gas curves from the appropriate ExtensoHeat datasheet for the gas being used to find the gas pressure needed at high fire This is the target value for high...

Page 13: ...iln s roof If the kiln is maintained in operation remove the burners and close the holes In case of kiln stop do not switch off the combustion blower until the kiln temperature is less than 572 F 300...

Page 14: ...ecklist 1 Test leak test safety shut off valves for tightness of closure 2 Test air pressure switch settings by checking switch movements against pressure settings and comparing with actual impulse pr...

Page 15: ...the main gas pressure regulator is too low Check start up setting Check regulator and adjust if necessary Not enough gas Start gas solenoid valve does not open Check solenoid valve coil for proper ori...

Page 16: ...out of adjustment Measure all gas pressures and air pressures Compare to initial start up settings and adjust where necessary Cannot achieve full capacity Gas pressure is too low into the main gas pr...

Page 17: ...er mm inch in 3 94 x 10 2 MJ Nm Btu ft standard 26 86 From To Multiply By kiloPascals kPa millibar mbar 10 meter m millimeter mm 1000 millibar mbar kiloPascals kPa 0 1 millimeter mm meter m 0 001 From...

Page 18: ...d Valve Normally Closed Solenoid valves are used to automatically shut off the gas supply on a bypass gas system or on small capacity burner systems 760 Manual Butterfly Valve Manual butterfly valve a...

Page 19: ...Installation Guide 235 5 23 2011...

Reviews: