Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
■
To avoid electric shock, shut off the power supply
when installing or removing any control device.
Flame monitoring systems must be installed by a
qualified, licensed technician.
DIP Switch Location
All of the DIP switches are located in the back of each
Veri-Flame unit (see Figure 3.1 on page 11, or the
photograph on page 7).
DIP Switch Access
To gain access to the DIP switches, the Veri-Flame must
be separated from the back box (for visual reference,
please refer to “Dimensions” on page 9). This separation
will expose the DIP switches on the back of the Veri-
Flame unit.
No Purge DIP Switch Settings
No Purge models of the Veri-Flame only use three of the
eight DIP switches, as shown in the labels in Figure 3.2 on
page 11. They are as follows:
SW1: Recycling mode selection (On = Recycling; Off =
Non-recycling)
SW2: Pilot selection (On = Intermittent, where pilot
remains on during burner cycle; Off = Interrupted, where
pilot valve closes after main burner is established).
SW3: Trial-for-ignition (TFI) range selection (For 5602/
5603 units: On = 10 seconds; Off = 5 seconds. For 5605
units: On = 10 seconds; Off = 15 seconds).
Modulation and Purge DIP Switch Settings
Modulation and purge models of the Veri-Flame use all of
the eight DIP switches, as illustrated in Figure 3.2 on page
11. They are as follows:
SW1: Recycling mode selection (On = Recycling; Off =
Non-recycling)
SW2: Pilot selection (On = Intermittent, where pilot
remains on during burner cycle; Off = Interrupted, where
pilot valve closes after main burner is established).
SW3: Trial-for-ignition (TFI) range selection (For 5602/
5603 units: On = 10 seconds; Off = 5 seconds. For 5605
units: On = 10 seconds; Off = 15 seconds).
SW4 through 7: Purge time selection. Total purge time is
the sum of each switch selected. If all are set off, the trial
for ignition starts when the air switch input comes on.
SW8: Post purge selection. (On = 15 second post purge).
Figure 3.1. DIP Switch Location
CAUTION
Close-up of DIP switches on
back side of all Veri-Flame models.