Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
28
Introduction
This section describes how the optional remote display is used with the Veri-Flame. The remote display provides LCD
messages which monitor the status of the Veri-Flame’s functions as well as any lockout conditions. This section is
divided into two parts or tables:
Veri-Flame Operating Sequence
This section describes the start-up and shutdown monitoring sequences of the Veri-Flame and how the progress (or halt)
of the sequence can be monitored by the messages on the remote display.
POWER ON
Was internal safe start check successful?
EXTERNAL INTERLOCK CHECKS
Is flame signal present?
BURNER START-UP
(see next page)
YES
NO
YES
NO
YES
NO
YES
NO
Various lockout messages
Fan output is energized; modulator is
sent to low fire.
YES
NO
Holds until answer is yes.
Is main valve closed switch made?*
* Applies to purge and no purge models only.
Is voltage present at air flow switch?
Is voltage present at interlock switch?
ERROR MESSAGE
MAIN VALVE FAIL
XX:XX:XX LOCKOUT
ERROR MESSAGE
LIMITS OPEN
TIME = XXXX:XX:XX
NORMAL MESSAGE
FAN ENERGIZED
ERROR MESSAGE #1
UNSAFE FLAME ON
NORMAL MESSAGE
REMOTE DISPLAY
REVISION X.X
Alarm energized.
Fan is energized. If signal is eliminated
within 30 seconds, sequence
continues. If not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE FLAME ON
XX:XX:XX LOCKOUT
ERROR MESSAGE #1
UNSAFE AIR SHORT
Alarm energized.
If switch is opened within 30 seconds,
sequence continues. If not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE AIR SHORT
XX:XX:XX LOCKOUT
FOR PURGE & MODULATING
NORMAL MESSAGE
SAFE START OK
Check_Sum = XX