Eclipse Veri-Flame Single Burner Monitoring System, Model 5600, V1, Installation Guide 818, 1/15/2015
LED Status and Conditions for Veri-Flame Purge Models
LED(s) Lit
Possible Cause
Interlocks Closed
The interlocks are closed (normal operation), power on terminal 7.
System Error
1. The flame detected is out of sequence, flame signal light is on.
2. The sensor is “runaway”, flame signal light is on.
3. Inductance is detected on sensor wires, flame signal light is on.
4. Voltage wired into terminals 3, 4 or 5.
5. Internal relay contacts welded.
6. Internal controller failure.
7. Air flow switch closed before start-up.
8. Main fuel valve switch opens after shutdown or before start-up, no power to V.
Flame Failure
1. Pilot flame is not established in selected TFI.
2. Main flame is not established in selected TFI.
3. Main flame fails within 35 seconds of TFI.
4. Flame failed during operation in non-recycle mode.
5. Flame failed 35 seconds after TFI and was not established after one try in recycle mode.
Air Failure
1. Air flow switch not closed within ten seconds of start-up.
2. Air flow switch is open during timing cycle.
3. Air flow switch is open during firing cycle.
Purge Model