ECI MOVFR-LCD Installation Manual
Electronic Controls, Inc.
7073 North Atlantic Ave. Cape Canaveral, FL 32920
800-633-9788
P a g e
|
15
5.1.5.1.3
Input Voltage setting Parameter
•
Input voltage –
Parameter
for setting valid AC/DC voltage for CLOSE, OPEN, NUDGE and
HEAVY inputs. Default setting is 24. Minimum is 12 and max is 240. Voltages below these
settings will not be detected by the control board.
5.1.5.1.4
Light Curtain Reopen enable
The last parameter in the list is the light curtain setting. To enable the on board light curtain input (see
section 5.1.2.3 Interfacing with Light Curtain) this parameter must be set to “1”. “0” is the default.
NOTE: Setting this parameter to “1” without a light curtain connected will cause to door to remain
open at all times.
5.1.5.2
Load Defaults
Selecting LOAD DEFAULTS will set all parameters to their default settings.
5.1.5.3
Diagnostics 1
Figure 7 - Diagnostics 1 Screen
VBUS
– present DC voltage for motor driver.
0s
– 16 second timer. Resets at each OPEN or CLOSE command. Will time down to 0 then all motor
drive is stopped until present command is cycled off then on or a new command is issued.
SPEED
– current speed of the motor. Reflects the actual speed setting.
TEMP
– Current temp of the output driver.
MOTOR
– Current to motor in amps.
CYCLE
– Number of cycles (OPEN and CLOSE) since manufacture.
5.1.5.4
Diagnostics 2
Selecting Diagnostic 2 will display the voltage present on any of the inputs:
•
Close Input
•
Open Input
•
Nudge Input
•
Heavy Input
ECI MOVFR
(C) 2018 ECI Inc.
VBUS : 317V 0s
SPEED : 0
TEMP : 29C/ 84F
MOTOR : .0A
CYCLE : xxxx (ESC)