background image

Echoflex Installation Guide

Temperature Sensor

Sensing Operation

The following features are available depending on the RTS model. The
receiving control equipment that the sensor is linked to uses its
configurable settings and interprets messages sent by the RTS.

Solar panel

Temperature dial

Test button

Fan control

Temperature and Humidity
Monitoring

: When there is

sufficient power, 100 lux (9 fc),
the sensor records the
temperature, temperature set
point, and humidity values every
10 seconds. If the light source is
poor, the sampling interval
increases to every 100 seconds. If
a period of low light reaches 24
hours, the interval increases to
every 200 seconds.

Temperature Set Point:

Create an

offset from the temperature set
point value that is set on the
receiving controller; rotate the
dial counterclockwise to lower and clockwise to increase. The receiving
control equipment interprets the set point value to an offset range. For
no offset, point the arrow on the dial straight up.

Fan Speed C ontrol:

(RTS-2HS model only) Adjust the fan speed by

selecting a setting: A (auto), O (off), 1 (low ), 2 (med), 3 (high) for the
receiving control equipment to interpret.

Test Button:

(RTS-2HS model only) Activate an occupied room state by

pressing the

[Test]

button on the right side of the sensor. This feature

engages all of the automated settings configured for the occupied space,
such as lights and heating. The receiving control equipment determines
the settings and timers.

Transmission Rate

The RTS transmits a message when:

10 sample values have been recorded.

The fan speed switch or the

[Test]

button are used.

The difference from the last transmitted temperature value is greater
than 0.3°C (0.5°F).

The difference from the last transmitted humidity value is greater
than 3%.

Temperature Sensor

Page 4 of 8

Echoflex

Summary of Contents for RTS

Page 1: ...nvironment of a space The RTS is available in two radio frequencies 902 MHz and 868 MHz The core model RTS 1T monitors temperature Additional models are available that also monitor relative humidity R...

Page 2: ...xtures in the space may disrupt wireless transmissions Install the sensor within range of linked receivers or controllers 24 m 80 ft Consider adding a repeater to extend reception range Before linking...

Page 3: ...double sided tape or Velcro not provided Over a standard Class 2 low voltage electrical box Keyholes in the back plate mate with standard screw patterns 1 Insert a flatblade screwdriver into the slot...

Page 4: ...ounterclockwise to lower and clockwise to increase The receiving control equipment interprets the set point value to an offset range For no offset point the arrow on the dial straight up Fan Speed Con...

Page 5: ...ransmission 4 Deactivate Link mode on the controller before attempting to link to any other controllers Battery Power A battery is not required for normal operation if the sensor receives adequate nat...

Page 6: ...LED 2 Press and hold the Test button again until the green LED stops blinking The green LED then repeats a number of blinks according to the detected light level The sensor reevaluates the light level...

Page 7: ...Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to operate the product Operation of this equipment in a resident...

Page 8: ...Echoflex Installation Guide Temperature Sensor Temperature Sensor Page 8 of 8 Echoflex...

Reviews: